Optimum PV Cleaning Interval for Soiling

Cleaning interval that minimises the cost of soiling losses plus cleaning for a PV plant with a steady soiling rate, with the average loss and yearly cost.

Thermal power plant

Inputs

Examples: Illustrative 5000 kWh/day, 0.2 %/day, 0.05, 1500 per cleanDesert 0.6 %/day, robot 300Rooftop 30 kWh/day, 0.1 %/day, 100

Accepted: 1 to 277,780 kWh
Accepted: 0.001 to 5 %
Accepted: 0.001 to 1
Accepted: 1 to 10,000,000

Results

Linear soiling: lost energy per day over an interval T averages E r T/2, so daily cost = E r T c_e/2 + C/T, minimised at T* = √(2C/(E r c_e)). Rain cleans arrays naturally; use the dry-season soiling rate.

Optimum interval (days)11.180
Average soiling loss at the optimum3.3541%
Cost of soiling and cleaning per day53.666
Cost per year19,588
Cleanings per year32.647

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 5000 kWh/day, 0.2 %/day, 0.05, 1500 per clean. The inputs, in the units selected above:

InputValue
Clean-array energy per day5,000.0 kWh
Soiling loss rate per day0.20000 %
Value of energy (currency per kWh)0.050000 -
Cost per cleaning (currency)1,500.0 -

Applying the formula below gives:

ResultValue
Optimum interval (days)77.460
Average soiling loss at the optimum7.7460 %
Cost of soiling and cleaning per day38.730
Cost per year14,136
Cleanings per year4.7121

Open this example in the calculator and change any input.

Formula

\(T^* = \sqrt{\frac{2C}{Erc_e}}, \quad c_{day,min} = \sqrt{2CErc_e}, \quad \bar l = \frac{rT^*}{2}\)

Variables

Symbol Meaning SI unit
\(E\) Clean-array energy per day J
\(r\) Soiling loss rate per day -
\(c_e\) Value of energy (currency per kWh) -
\(C\) Cost per cleaning (currency) -
\(T^*\) Optimum interval (days) -
\(\bar l\) Average soiling loss at the optimum -
\(c_{day}\) Cost of soiling and cleaning per day -
\(c_{year}\) Cost per year -
\(n\) Cleanings per year -

Method and standards

Cleaning optimisation.

Where it is used

  • PV O&M planning in dusty climates.
  • Comparing robotic and manual cleaning.

Common mistakes

  • Using the wet-season soiling rate.
  • Ignoring water and access costs in C.

Assumptions and limits

  • Constant soiling rate; full recovery at each cleaning.

References

  • Economic interval for a linearly growing loss

Questions and answers

How fast do panels get dirty?

From under 0.1 % a day in rainy climates to 0.5–1 % a day in deserts; dust storms add sudden steps.

Why a square root?

Losses grow with the interval while cleaning costs shrink with it; the balance gives T* proportional to √(C/(E r c_e)).

What do the defaults represent?

An illustrative plant making 5,000 kWh a day clean, soiling 0.2 % a day, energy worth 0.05 per kWh and 1,500 per cleaning.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Gilbert Masters, Renewable and Efficient Electric Power Systems (Wiley, 2004), ch. 9

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.