FireCADCalc

PV System Size for an Annual Electricity Consumption

PV capacity, number of modules and roof area to supply a share of a building's annual electricity from the site's specific yield and the module rating and size.

Thermal power plant

Inputs

Examples: Illustrative home 12000 kWhOffice 200 MWh, half coveredSunny site 5000 kWh

Accepted: 1 to 277,780,000 kWh
Accepted: 5 to 200 %
Accepted: 400 to 2,500
Accepted: 0.05 to 1 kW
Accepted: 0.3 to 4 m²
Accepted: 1 to 3

Results

kWp = f·E/Y; specific yield already includes system losses (use a value for the site, tilt and orientation). Covering the annual total does not mean covering every hour: most of the PV output is exported in summer and imported back in winter without storage.

PV capacity needed2.7778kW
Modules7.0000
Installed with whole modules2.8000kW
Roof area needed15.960m²
Annual PV generation5.0400MWh

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative home 12000 kWh. The inputs, in the units selected above:

InputValue
Annual electricity consumption12,000 kWh
Share of consumption to cover100.00 %
Specific yield (kWh per kWp per year)1,450.0 -
Module rating0.43000 kW
Module area1.9500 m²
Roof area factor (gaps, access; 1.1–1.3)1.2000 -

Applying the formula below gives:

ResultValue
PV capacity needed8.2759 kW
Modules20.000
Installed with whole modules8.6000 kW
Roof area needed46.800 m²
Annual PV generation12.470 MWh

Open this example in the calculator and change any input.

Formula

\(P_{PV} = \frac{fE}{Y}, \quad n = \left\lceil\frac{P_{PV}}{P_m}\right\rceil, \quad A = nA_mk_A\)

Variables

Symbol Meaning SI unit
\(E\) Annual electricity consumption J
\(f\) Share of consumption to cover -
\(Y\) Specific yield (kWh per kWp per year) -
\(P_m\) Module rating W
\(A_m\) Module area m²
\(k_A\) Roof area factor (gaps, access; 1.1–1.3) -
\(P_{PV}\) PV capacity needed W
\(n\) Modules -
\(P\) Installed with whole modules W
\(A\) Roof area needed m²
\(E_{PV}\) Annual PV generation J

Method and standards

PV sizing by annual energy.

Where it is used

  • Home and commercial PV proposals.
  • Net-zero building checks.

Common mistakes

  • Using peak sun hours of one month as the annual yield.
  • Ignoring shading and orientation in the yield.

Assumptions and limits

  • Annual energy balance only.

References

  • Annual energy balance for PV sizing

Questions and answers

How big a system covers a typical home?

About 1 kWp per 1,000–1,600 kWh a year depending on sunshine: 12,000 kWh needs about 8 kWp at 1,450 kWh/kWp.

Does covering the annual total make a home self-sufficient?

No: summer surplus is exported and winter evenings are imported; self-sufficiency is usually 30–40 % without a battery.

What do the defaults represent?

An illustrative home using 12,000 kWh a year, fully covered, at a specific yield of 1,450 kWh/kWp with 430 W, 1.95 m² modules.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Gilbert Masters, Renewable and Efficient Electric Power Systems (Wiley, 2004), ch. 9

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.