FireCADCalc

Surge Impedance and Surge Impedance Loading

Surge (characteristic) impedance and surge impedance loading (natural load) of a line or cable from its inductance and capacitance per km, with wave velocity.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: 220 kV overhead400 kV quad bundle

Results

At SIL, reactive power generated by line capacitance equals that absorbed by its inductance and voltage is flat along the line. Overhead lines are about 300–400 Ω; cables 30–60 Ω.

Surge impedance294.88Ω
Surge impedance loading164.13MW
Wave velocity294,884km/s

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 220 kV overhead. The inputs, in the units selected above:

InputValue
Line voltage220.00 kV
Inductance (mH/km)1.0000 -
Capacitance (nF/km)11.500 -

Applying the formula below gives:

ResultValue
Surge impedance294.88 Ω
Surge impedance loading164.13 MW
Wave velocity294,884 km/s

Open this example in the calculator and change any input.

Formula

\(Z_c = \sqrt{\frac{L'}{C'}}, \quad SIL = \frac{V^2}{Z_c}, \quad v_w = \frac{1}{\sqrt{L'C'}}\)

Variables

Symbol Meaning SI unit
\(V\) Line voltage V
\(L'\) Inductance (mH/km) -
\(C'\) Capacitance (nF/km) -
\(Z_c\) Surge impedance Ω
\(SIL\) Surge impedance loading W
\(v_w\) Wave velocity m/s

Method and standards

Lossless line.

Where it is used

  • Line loadability studies.
  • Reactive compensation planning.

Common mistakes

  • Using phase voltage in SIL.
  • Per-km values in the wrong units.

Assumptions and limits

  • Lossless line (R and G neglected). L' is entered in mH/km and C' in nF/km; the page warns if their product gives a wave velocity above the speed of light, which means the two values are inconsistent.

  • Lossless line.

References

  • Stevenson and Grainger
  • Power System Analysis (McGraw-Hill, 1994); Kothari and Nagrath
  • Modern Power System Analysis
  • 4th ed. (2011) (Z_c = √(L/C), SIL = V²/Z_c)

Questions and answers

What does loading above SIL mean?

The line absorbs reactive power and voltage sags along it; below SIL it generates reactive power and voltage rises.

Why are cables so different?

Their high capacitance gives low surge impedance and a very high SIL; they are always lightly loaded relative to it.

What do the defaults represent?

A 220 kV overhead line with 1 mH/km and 11.5 nF/km.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.