FireCADCalc

Overhead Line Inductance and Capacitance from Conductor Spacing

Inductance, capacitance, reactance and susceptance per km of a three-phase overhead line from conductor radius and the spacing between phases.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: 25 mm conductor, flat 4–4–8 mEquilateral 2 m, 10 mm radius

Results

Solid round conductor (GMR = 0.7788r) and a fully transposed line; stranded and bundled conductors use the maker's GMR. Earth effect on capacitance neglected.

Geometric mean distance5.0397m
Inductance per length1.2499mH/km
Reactance (Ω/km)0.39266
Capacitance to neutral per length9.2731nF/km
Susceptance (µS/km)2.9132

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 25 mm conductor, flat 4–4–8 m. The inputs, in the units selected above:

InputValue
Conductor radius12.500 mm
Spacing phase 1–24.0000 m
Spacing phase 2–34.0000 m
Spacing phase 3–18.0000 m
Frequency50.000 Hz

Applying the formula below gives:

ResultValue
Geometric mean distance5.0397 m
Inductance per length1.2499 mH/km
Reactance (Ω/km)0.39266
Capacitance to neutral per length9.2731 nF/km
Susceptance (µS/km)2.9132

Open this example in the calculator and change any input.

Formula

\(GMD = \sqrt[3]{D_{12}D_{23}D_{31}}, \quad L' = 2\times10^{-7}\ln\frac{GMD}{0.7788r}, \quad C' = \frac{2\pi\varepsilon_0}{\ln(GMD/r)}\)

Variables

Symbol Meaning SI unit
\(r\) Conductor radius m
\(D_{12}\) Spacing phase 1–2 m
\(D_{23}\) Spacing phase 2–3 m
\(D_{31}\) Spacing phase 3–1 m
\(f\) Frequency 1/s
\(GMD\) Geometric mean distance m
\(L'\) Inductance (mH/km) -
\(X'\) Reactance (Ω/km) -
\(C'\) Capacitance to neutral (nF/km) -
\(B'\) Susceptance (µS/km) -

Method and standards

Line constants.

Where it is used

  • Plant overhead lines.
  • Fault and load-flow data.

Common mistakes

  • Using diameter for radius.
  • Ignoring bundle GMR.

Assumptions and limits

  • Transposed; solid conductors. There is no GMR input: for stranded (ACSR) or bundled conductors the maker's GMR differs from 0.7788r, so the inductance here is approximate.
  • L′ = 2 × 10⁻⁷ ln(GMD/GMR) H/m uses the classical μ₀/2π = 2 × 10⁻⁷. Results are shown in mH/km, Ω/km, nF/km and µS/km in every unit system.

References

  • Stevenson and Grainger
  • Power System Analysis (McGraw-Hill, 1994); Kothari and Nagrath
  • Modern Power System Analysis
  • 4th ed. (2011) (L = 2×10⁻⁷ ln(GMD/GMR) H/m, C = 2πε₀/ln(GMD/r) F/m)

Questions and answers

Why does wider spacing raise inductance?

More flux links the loop between conductors; inductance grows with the log of spacing.

What is GMR?

The radius of an equivalent thin-walled conductor with the same internal plus external flux: 0.7788r for a solid round wire.

What do the defaults represent?

A 25 mm diameter conductor in a flat 4–4–8 m configuration at 50 Hz.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.