Energy Meter Multiplying Factor from CT and PT Ratios

Multiplying factor of a CT- and PT-operated energy meter from the installed and meter-programmed ratios, and the actual energy from the meter reading difference.

Thermal power plantProcess steam and utilities

Inputs

Examples: HT meter 200/5 A, 11 kV/110 V, 1 500 kWh readLT meter 800/5 A, no PT, 2 340 kWh readMeter programmed 100/5 on a 400/5 CT, 33 kV/110 V

Results

If the meter is programmed with the full CT and PT ratios it reads primary energy directly and the factor is 1; check the meter's display settings.

Installed CT ratio160.00
Installed PT ratio1.0000
Multiplying factor160.00
Actual energy374,400kWh

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: HT meter 200/5 A, 11 kV/110 V, 1 500 kWh read. The inputs, in the units selected above:

InputValue
CT primary current200.00 A
CT secondary current5.0000 A
PT primary voltage (equal to secondary if no PT)11,000 V
PT secondary voltage110.00 V
CT ratio programmed in the meter (1 = none)1.0000 -
PT ratio programmed in the meter (1 = none)1.0000 -
Meter reading difference1,500.0 kWh

Applying the formula below gives:

ResultValue
Installed CT ratio40.000
Installed PT ratio100.00
Multiplying factor4,000.0
Actual energy6,000,000 kWh

Open this example in the calculator and change any input.

Formula

\(k_{CT} = I_{1}/I_{2}, \quad k_{PT} = U_{1}/U_{2}\)

\(MF = \frac{k_{CT}\, k_{PT}}{k_{CT,m}\, k_{PT,m}}\)

\(E = MF \cdot \Delta R\)

Variables

Symbol Meaning SI unit
\(I_{1}\) CT primary current A
\(I_{2}\) CT secondary current A
\(U_{1}\) PT primary voltage V
\(U_{2}\) PT secondary voltage V
\(k_{CT,m}\) CT ratio programmed in the meter -
\(k_{PT,m}\) PT ratio programmed in the meter -
\(\Delta R\) meter reading difference J
\(k_{CT}\) installed CT ratio -
\(k_{PT}\) installed PT ratio -
\(MF\) multiplying factor -
\(E\) actual energy J

Method and standards

A transformer-operated meter sees secondary quantities; the multiplying factor restores primary energy. Whatever ratio is already programmed into the meter is divided out.

Where it is used

  • Checking utility bills and sub-meter readings.
  • Commissioning new HT meters.
  • Reconciling plant energy balances.

Common mistakes

  • Applying MF to a meter already programmed for primary readings.
  • Using the wrong CT tap.
  • Forgetting the PT ratio on HT meters.

Assumptions and limits

  • Ideal CT and PT ratios; instrument transformer errors not included.

References

  • MF = (CT ratio × PT ratio) / ratios set in the meter

Questions and answers

What is the MF of a meter on 200/5 A CTs and 11 kV/110 V PTs?

40 × 100 = 4 000, so 1 500 kWh on the meter is 6 000 MWh actually consumed (when the meter itself has no ratio programmed).

What if the meter is programmed with a different CT ratio?

Divide by what the meter already applies: a meter set to 100/5 on a 400/5 CT needs a factor of 4 for the CT.

Is MF needed on an LT meter without PTs?

Only the CT ratio: an 800/5 A CT meter has MF 160.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.