Energy Meter Accuracy Test (Pulses or Revolutions)

Error of an energy meter from its constant in impulses or revolutions per kWh, the pulses counted, the time taken and the true load during the test.

Thermal power plantProcess steam and utilities

Inputs

Examples: 3 200 imp/kWh, 32 pulses in 35.5 s at 1 kW1 600 imp/kWh, 20 pulses in 22 s at 2 kW600 rev/kWh, 10 revolutions in 61 s at 1 kW

Results

Energy recorded by the meter0.016667kWh
True energy0.016944kWh
Meter error (positive = reads fast)-1.6393%
Time a correct meter would take60.000s

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 3 200 imp/kWh, 32 pulses in 35.5 s at 1 kW. The inputs, in the units selected above:

InputValue
Meter constant (impulses or revolutions per kWh)3,200.0 -
Pulses or revolutions counted32.000 -
Time taken35.500 s
True load during the test1,000.0 W

Applying the formula below gives:

ResultValue
Energy recorded by the meter0.010000 kWh
True energy0.009861 kWh
Meter error (positive = reads fast)1.4085 %
Time a correct meter would take36.000 s

Open this example in the calculator and change any input.

Formula

\(E_m = \frac{n}{K}, \quad \varepsilon = \frac{E_m - P\, t}{P\, t}\)

Variables

Symbol Meaning SI unit
\(K\) Meter constant (impulses or revolutions per kWh) -
\(n\) Pulses or revolutions counted -
\(t\) Time taken s
\(P\) True load during the test W
\(E_m\) Energy recorded by the meter J
\(E_t\) True energy J
\(\varepsilon\) Meter error (positive = reads fast) -
\(t_0\) Time a correct meter would take s

Method and standards

Recorded energy from the meter constant compared with the true energy.

Where it is used

  • Site checks of tariff and sub-meters.
  • Electrician practice.

Common mistakes

  • Using the nameplate load as true load.
  • Too few pulses.

Assumptions and limits

  • Steady load during the test.

References

  • Meter constant definition; error = (recorded − true) / true

Questions and answers

A 3200 imp/kWh meter gives 32 pulses in 35.5 s on a 1000 W load. What is its error?

Recorded 0.01 kWh; true 0.00986 kWh; error +1.4 %.

How long should the test be?

Long enough that one pulse of timing error is small: 30 or more pulses.

What is the true load?

From a reference meter or a known resistive load and measured voltage.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.