Diesel Generator (DG Set) Fuel Consumption and Cost per kWh

Diesel consumption per hour and per day of a DG set from load and specific fuel consumption, with units generated per litre and the fuel cost per kWh.

Thermal power plantProcess steam and utilities

Inputs

Examples: 400 kW at 240 g/kWh, 8 h a day1 MW at 210 g/kWh, 24 h62.5 kVA set at 50 kW, 270 g/kWh, 4 h

From the maker's data sheet at your load; it rises at part load.

Results

Fuel only: lubricating oil, maintenance and the set's capital cost add to the cost per kWh.

Fuel mass flow13.500kg/h
Fuel volume flow0.26786L/min
Fuel per day64.286L
Electricity per litre of fuel3.1111kWh/L
Fuel cost per kWh28.929
Fuel cost per day5,785.7

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 400 kW at 240 g/kWh, 8 h a day. The inputs, in the units selected above:

InputValue
Electrical load on the set400.00 kW
Specific fuel consumption at that load, per electrical kWh at the terminals240.00 g/kWh
Fuel density840.00 kg/m³
Running hours per day8.0000 h
Fuel price per litre (your currency)90.000 -

Applying the formula below gives:

ResultValue
Fuel mass flow96.000 kg/h
Fuel volume flow1.9048 L/min
Fuel per day914.29 L
Electricity per litre of fuel3.5000 kWh/L
Fuel cost per kWh25.714
Fuel cost per day82,286

Open this example in the calculator and change any input.

Formula

\(\dot m_F = P \cdot SFC, \quad \dot V_F = \dot m_F / \rho, \quad V_d = \dot V_F\, t\)

\(e_L = \rho / SFC, \quad c_{kWh} = c \cdot \frac{SFC}{\rho}\)

Variables

Symbol Meaning SI unit
\(P\) Electrical load on the set W
\(SFC\) Specific fuel consumption at that load, per electrical kWh at the terminals kg/J
\(\rho\) Fuel density kg/m³
\(t\) Running hours per day s
\(c\) Fuel price per litre (your currency) -
\(\dot m_F\) Fuel mass flow kg/s
\(\dot V_F\) Fuel volume flow m³/s
\(V_d\) Fuel per day m³
\(e_L\) Electricity per litre of fuel J/m³
\(c_{kWh}\) Fuel cost per kWh -
\(C_d\) Fuel cost per day -

Method and standards

Fuel flow is load times specific fuel consumption from the maker's data at that load; dividing by density gives litres. The cost per kWh is the litres per kWh times the price per litre.

Where it is used

  • Budgeting DG running costs.
  • Comparing DG power with grid or captive power.
  • Checking for fuel theft or a worn engine against expected consumption.

Common mistakes

  • Using the full-load SFC at part load (SFC rises as load falls).
  • Using kVA instead of kW load.
  • Mixing litres at different temperatures.

Assumptions and limits

  • Steady load; SFC from the maker at that load.
  • SFC per electrical kWh at the generator terminals. An engine data sheet (ISO 3046) gives SFC per shaft kWh: divide it by the alternator efficiency (about 0.93–0.96) first, or the fuel is understated by 4–7 %.
  • Fuel cost only.

References

  • Specific fuel consumption definition (ISO 8528 / ISO 3046 rating practice)

Questions and answers

How much diesel does a 400 kW load take?

At 240 g/kWh, 96 kg/h, or about 114 L/h at 840 kg/m³; 914 L for 8 hours.

How many units per litre?

3.5 kWh per litre in that case; a well-loaded large set reaches about 4 kWh/L, a lightly loaded small one much less.

What does the fuel cost per kWh?

About 25.7 at 90 per litre, before lubricating oil, maintenance and the set's capital cost.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.