Worked example
Example: 415 V, 10 Ω per phase, 0.8, star. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Line voltage | 415.00 V |
| Impedance per phase | 10.000 Ω |
| Power factor of the load | 0.80000 - |
| Connection | Star (Y) |
Applying the formula below gives:
| Result | Value |
|---|---|
| Phase voltage | 239.60 V |
| Phase current | 23.960 A |
| Line current | 23.960 A |
| Active power | 13.778 kW |
| Apparent power | 17.223 kVA |
Open this example in the calculator and change any input.
Formula
\(\text{Star: } V_{ph} = \frac{V_L}{\sqrt 3},\ I_L = I_{ph}; \quad \text{Delta: } V_{ph} = V_L,\ I_L = \sqrt 3\, I_{ph}\)
\(P = 3 V_{ph} I_{ph} \cos\varphi = \sqrt 3\, V_L I_L \cos\varphi\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(V_L\) | Line voltage | V |
| \(Z\) | Impedance per phase | Ω |
| \(\cos\varphi\) | Power factor of the load | - |
| \(\text{conn}\) | Connection | - |
| \(V_{ph}\) | Phase voltage | V |
| \(I_{ph}\) | Phase current | A |
| \(I_L\) | Line current | A |
| \(P\) | Active power | W |
| \(S\) | Apparent power | VA |
Method and standards
Balanced star and delta relations.
Where it is used
- Heater banks and motor windings.
- Electrical examinations.
Common mistakes
- Mixing line and phase values.
- Forgetting the factor 3 between star and delta.
Assumptions and limits
- Balanced load.
- The power factor is entered separately and is not checked against the impedance: for an impedance R + jX it should be R/Z.
References
- Balanced three-phase circuit relations (textbook)
Questions and answers
What do 10 Ω per phase draw in star on 415 V?
Phase voltage 239.6 V, current 23.96 A.
And in delta?
Phase current 41.5 A, line current 71.9 A: three times the star line current.
Is P = √3 V_L I_L cos φ true for both?
Yes, with line values.