Worked example
Example: Delta 30, 60, 90 Ω to star. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Conversion | Delta to star (R_ab, R_bc, R_ca → R_a, R_b, R_c) |
| First resistance: R_ab (delta) or R_a (star) | 30.000 Ω |
| Second resistance: R_bc (delta) or R_b (star) | 60.000 Ω |
| Third resistance: R_ca (delta) or R_c (star) | 90.000 Ω |
Applying the formula below gives:
| Result | Value |
|---|---|
| First result: R_a (star) or R_ab (delta) | 15.000 Ω |
| Second result: R_b (star) or R_bc (delta) | 10.000 Ω |
| Third result: R_c (star) or R_ca (delta) | 30.000 Ω |
Open this example in the calculator and change any input.
Formula
\(R_a = \frac{R_{ab} R_{ca}}{R_{ab} + R_{bc} + R_{ca}}, \quad R_b = \frac{R_{ab} R_{bc}}{\Sigma}, \quad R_c = \frac{R_{bc} R_{ca}}{\Sigma}\)
\(R_{ab} = \frac{R_a R_b + R_b R_c + R_c R_a}{R_c}, \quad R_{bc} = \frac{\cdots}{R_a}, \quad R_{ca} = \frac{\cdots}{R_b}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\text{direction}\) | Conversion | - |
| \(R_1\) | First resistance: R_ab (delta) or R_a (star) | Ω |
| \(R_2\) | Second resistance: R_bc (delta) or R_b (star) | Ω |
| \(R_3\) | Third resistance: R_ca (delta) or R_c (star) | Ω |
| \(R'_1\) | First result: R_a (star) or R_ab (delta) | Ω |
| \(R'_2\) | Second result: R_b (star) or R_bc (delta) | Ω |
| \(R'_3\) | Third result: R_c (star) or R_ca (delta) | Ω |
| \(R_{ab}, R_{bc}, R_{ca}\) | Delta resistances between terminals | Ω |
| \(R_a, R_b, R_c\) | Star resistances from each terminal to the star point | Ω |
| \(\Sigma\) | Sum of the delta resistances | Ω |
Method and standards
Kennelly's transformation makes a delta and a star of resistances look the same between each pair of terminals. Here R₁, R₂, R₃ are R_ab, R_bc, R_ca for a delta or R_a, R_b, R_c for a star, and the results follow the same order.
Where it is used
- Reducing bridge networks that are neither series nor parallel.
- Converting three-phase loads to per-phase star values.
- Earth grid and filter calculations.
Common mistakes
- Mixing up which star arm sits opposite which delta side.
- Using magnitudes for impedances of different phase angles.
- Forgetting a balanced delta is three times the star.
Assumptions and limits
- Linear passive elements.
- Magnitudes only: exact for resistances, and for impedances only when all three have the same phase angle. Mixed R, L and C elements need the complex form.
References
- A.E. Kennelly (1899)
- star–delta transformation
Questions and answers
What star is equal to a delta of 30, 60 and 90 Ω?
R_a = 15 Ω, R_b = 10 Ω and R_c = 30 Ω: each star arm is the product of the two adjacent delta sides over their sum.
What delta is equal to a star of three 10 Ω?
Three 30 Ω: a balanced delta is three times the balanced star.
Does it work for impedances?
Yes with complex numbers; this page uses magnitudes, which is exact only when all three have the same phase angle.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.