Worked example
Example: 3 kW at 210 V. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Rated power | 3.0000 kW |
| Rated voltage | 230.00 V |
| Actual voltage | 210.00 V |
Applying the formula below gives:
| Result | Value |
|---|---|
| Resistance V²/P | 17.633 Ω |
| Rated current | 13.043 A |
| Power at the actual voltage | 2.5009 kW |
| Current at the actual voltage | 11.909 A |
Open this example in the calculator and change any input.
Formula
\(R = \frac{V_r^2}{P_r}, \quad P = \frac{V^2}{R}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(P_r\) | Rated power | W |
| \(V_r\) | Rated voltage | V |
| \(V\) | Actual voltage | V |
| \(R\) | Resistance V²/P | Ω |
| \(I_r\) | Rated current | A |
| \(P\) | Power at the actual voltage | W |
| \(I\) | Current at the actual voltage | A |
Method and standards
Ohm's law.
Where it is used
- Heaters, ovens and tracing.
- Electrician examinations.
Common mistakes
- Assuming power is constant.
- Using line voltage for star-connected elements.
Assumptions and limits
- Constant resistance.
References
- Ohm's law and P = V²/R
Questions and answers
3 kW, 230 V heater on 210 V?
R 17.63 Ω; power falls to 2.50 kW.
Why does power fall so much?
It goes with the square of voltage.
Three-phase heaters?
Apply per element with its own voltage (phase or line).