Star and Delta: Line and Phase Voltage, Current and Power

Phase voltage, phase and line current and power of a balanced three-phase load connected in star or delta, from line voltage and impedance per phase.

Thermal power plantProcess steam and utilitiesElectrician and wireman licence examinations

Inputs

Examples: 415 V, 10 Ω per phase, 0.8, star415 V, 10 Ω per phase, 0.8, delta11 kV, 60 Ω, unity, star

Results

The same impedances take three times the line current and power in delta as in star: the basis of star–delta starting.

Phase voltage6,350.9V
Phase current105.85A
Line current105.85A
Active power2,016.7kW
Apparent power2,016.7kVA

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 415 V, 10 Ω per phase, 0.8, star. The inputs, in the units selected above:

InputValue
Line voltage415.00 V
Impedance per phase10.000 Ω
Power factor of the load0.80000 -
ConnectionStar (Y)

Applying the formula below gives:

ResultValue
Phase voltage239.60 V
Phase current23.960 A
Line current23.960 A
Active power13.778 kW
Apparent power17.223 kVA

Open this example in the calculator and change any input.

Formula

\(\text{Star: } V_{ph} = \frac{V_L}{\sqrt 3},\ I_L = I_{ph}; \quad \text{Delta: } V_{ph} = V_L,\ I_L = \sqrt 3\, I_{ph}\)

\(P = 3 V_{ph} I_{ph} \cos\varphi = \sqrt 3\, V_L I_L \cos\varphi\)

Variables

Symbol Meaning SI unit
\(V_L\) Line voltage V
\(Z\) Impedance per phase Ω
\(\cos\varphi\) Power factor of the load -
\(\text{conn}\) Connection -
\(V_{ph}\) Phase voltage V
\(I_{ph}\) Phase current A
\(I_L\) Line current A
\(P\) Active power W
\(S\) Apparent power VA

Method and standards

Balanced star and delta relations.

Where it is used

  • Heater banks and motor windings.
  • Electrical examinations.

Common mistakes

  • Mixing line and phase values.
  • Forgetting the factor 3 between star and delta.

Assumptions and limits

  • Balanced load.
  • The power factor is entered separately and is not checked against the impedance: for an impedance R + jX it should be R/Z.

References

  • Balanced three-phase circuit relations (textbook)

Questions and answers

What do 10 Ω per phase draw in star on 415 V?

Phase voltage 239.6 V, current 23.96 A.

And in delta?

Phase current 41.5 A, line current 71.9 A: three times the star line current.

Is P = √3 V_L I_L cos φ true for both?

Yes, with line values.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.