Motor Starting (Acceleration) Time

Time for a motor to run a load up to speed from the total moment of inertia and the average motor and load torques, with the stored kinetic energy.

Thermal power plantProcess steam and utilities

Inputs

Examples: 12 kg·m², 1 480 rpm, 700 and 250 N·mID fan: 180 kg·m², 990 rpm, 2 400 and 900 N·m0.4 kg·m², 2 950 rpm, 60 and 20 N·m

Results

Refer load inertia to the motor shaft by the square of the speed ratio. A long start heats the motor: compare with the maker's permitted starting time.

Average accelerating torque40.000N·m
Starting time3.0892s
Kinetic energy at full speed19.087kJ

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 12 kg·m², 1 480 rpm, 700 and 250 N·m. The inputs, in the units selected above:

InputValue
Total moment of inertia at the motor shaft12.000 kg·m²
Final speed1,480.0 rpm
Average motor torque during the start700.00 N·m
Average load torque during the start250.00 N·m

Applying the formula below gives:

ResultValue
Average accelerating torque450.00 N·m
Starting time4.1329 s
Kinetic energy at full speed144.12 kJ

Open this example in the calculator and change any input.

Formula

\(t_s = \frac{J\, \omega}{T_m - T_l}, \quad \omega = 2\pi N, \quad E_k = \tfrac12 J \omega^2\)

Variables

Symbol Meaning SI unit
\(J\) Total moment of inertia at the motor shaft kg·m²
\(N\) Final speed 1/s
\(T_m\) Average motor torque during the start N·m
\(T_l\) Average load torque during the start N·m
\(T_a\) Average accelerating torque N·m
\(t_s\) Starting time s
\(E_k\) Kinetic energy at full speed J

Method and standards

Constant average accelerating torque.

Where it is used

  • Large fans, centrifuges and mills.
  • Setting overload relay classes.

Common mistakes

  • Leaving out the load inertia.
  • Inertia not referred through the gear ratio.

Assumptions and limits

  • Average torques; no voltage dip. The average-torque method can be unconservative when the load curve approaches the motor curve near pull-up (fans): integrate over the torque–speed curves step by step in that case.

References

  • Newton's second law for rotation
  • J dω/dt = T_m − T_l

Questions and answers

How long to reach 1480 rpm with 12 kg·m², 700 N·m motor and 250 N·m load torque?

4.1 s.

Where do the average torques come from?

From the motor and load torque–speed curves; a common estimate for a DOL start is the mean of starting and pull-out torque.

Why does it matter?

Fans with high inertia can start for 20 s or more and trip thermal protection.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.