FireCADCalc

IGBT Conduction and Switching Losses and Junction Temperature

Conduction and switching losses of an IGBT from its on-state model and switching energies scaled to the operating voltage and current, and the junction temperature.

Inputs

Examples: Illustrative 100 A IGBT at 8 kHzLow-frequency driveFast UPS inverter

Accepted: 0 to 5 V
Accepted: 0 to 1,000 mΩ
Accepted: 0 to 10,000 A
Accepted: 0 to 10,000 A
Accepted: 0 to 10,000 mJ
Accepted: 0 to 10,000 mJ
Accepted: 1 to 5,000 V
Accepted: 0.1 to 10,000 A
Accepted: 1 to 5,000 V
Accepted: 0 to 10,000 A
Accepted: 0.001 to 1,000 kHz
Accepted: 0 to 10
Accepted: 0 to 10
Accepted: -40 to 100 °C

Results

The on-state voltage is modelled as V_CE0 + r_CE i, so conduction loss is V_CE0 I_av + r_CE I_rms². Switching energies from the datasheet are scaled linearly to the actual DC-link voltage and switched current, then multiplied by the switching frequency. The junction temperature is ambient plus total loss through the thermal resistances. Use datasheet values at the expected junction temperature (usually 125 or 150 °C) and keep a margin below the maximum; add the free-wheeling diode's losses separately.

Conduction loss67.800W
Switching loss23.520W
Total loss91.320W
Case temperature71.962°C
Junction temperature94.792°C

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 100 A IGBT at 8 kHz. The inputs, in the units selected above:

InputValue
On-state threshold voltage0.90000 V
On-state slope resistance12.000 mΩ
Average current in the switch35.000 A
RMS current in the switch55.000 A
Turn-on energy at the datasheet point3.5000 mJ
Turn-off energy at the datasheet point2.8000 mJ
Datasheet test voltage600.00 V
Datasheet test current100.00 A
DC link voltage560.00 V
Average current switched50.000 A
Switching frequency8.0000 kHz
Junction-to-case thermal resistance (K/W)0.25000 -
Case-to-ambient (interface and heat sink) thermal resistance (K/W)0.35000 -
Ambient temperature40.000 °C

Applying the formula below gives:

ResultValue
Conduction loss67.800 W
Switching loss23.520 W
Total loss91.320 W
Case temperature71.962 °C
Junction temperature94.792 °C

Open this example in the calculator and change any input.

Formula

\(P_{cond} = V_{CE0}I_{av} + r_{CE}I_{rms}^2, \quad P_{sw} = (E_{on} + E_{off}) f_s \frac{V_{dc}}{V_{ref}}\frac{I_{sw}}{I_{ref}}, \quad T_j = T_a + P(R_{\theta JC} + R_{\theta CA})\)

Variables

Symbol Meaning SI unit
\(V_{CE0}\) On-state threshold voltage V
\(r_{CE}\) On-state slope resistance Ω
\(I_{av}\) Average current in the switch A
\(I_{rms}\) RMS current in the switch A
\(E_{on}\) Turn-on energy at the datasheet point J
\(E_{off}\) Turn-off energy at the datasheet point J
\(V_{ref}\) Datasheet test voltage V
\(I_{ref}\) Datasheet test current A
\(V_{dc}\) DC link voltage V
\(I_{sw}\) Average current switched A
\(f_s\) Switching frequency 1/s
\(R_{\theta JC}\) Junction-to-case thermal resistance (K/W) -
\(R_{\theta CA}\) Case-to-ambient (interface and heat sink) thermal resistance (K/W) -
\(T_a\) Ambient temperature K
\(P_{cond}\) Conduction loss W
\(P_{sw}\) Switching loss W
\(P\) Total loss W
\(T_c\) Case temperature K
\(T_j\) Junction temperature K

Method and standards

IGBT losses.

Where it is used

  • Inverter and drive thermal design.
  • Choosing switching frequency and heat sinks.

Common mistakes

  • Using switching energies at 25 °C.
  • Forgetting the diode losses in the same module.

Assumptions and limits

  • Linear scaling; steady-state temperatures.

References

  • Piecewise-linear on-state model and linear scaling of switching energies

Questions and answers

How do I scale the datasheet switching energy?

Linearly with voltage and current: E = E_ref (V/V_ref)(I/I_ref), at the same gate resistance and temperature.

Why use RMS current for the resistive part?

The loss in a resistance depends on the square of the current, averaged over time.

What do the defaults represent?

An illustrative 100 A, 1200 V IGBT in an inverter on a 560 V link at 8 kHz, 40 °C ambient.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Mohan, Undeland and Robbins, Power Electronics, 3rd ed. (Wiley, 2003)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.