Worked example
Example: Illustrative mixed delta at 415 V. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Line voltage | 415.00 V |
| Branch AB resistance | 20.000 Ω |
| Branch AB reactance | 10.000 Ω |
| Branch BC resistance | 30.000 Ω |
| Branch BC reactance | 0 Ω |
| Branch CA resistance | 15.000 Ω |
| Branch CA reactance | -10.000 Ω |
Applying the formula below gives:
| Result | Value |
|---|---|
| Line current A | 41.579 A |
| Line current B | 23.803 A |
| Line current C | 26.082 A |
| Total active power | 20.579 kW |
| Total reactive power | -1.8547 kvar |
Open this example in the calculator and change any input.
Formula
\(I_{ab} = \frac{V_{ab}}{Z_{ab}}, \quad I_A = I_{ab} - I_{ca}, \quad S = \sum V_{xy}I_{xy}^*\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(V_{LL}\) | Line voltage | V |
| \(R_{ab}\) | Branch AB resistance | Ω |
| \(X_{ab}\) | Branch AB reactance | Ω |
| \(R_{bc}\) | Branch BC resistance | Ω |
| \(X_{bc}\) | Branch BC reactance | Ω |
| \(R_{ca}\) | Branch CA resistance | Ω |
| \(X_{ca}\) | Branch CA reactance | Ω |
| \(I_A\) | Line current A | A |
| \(I_B\) | Line current B | A |
| \(I_C\) | Line current C | A |
| \(P\) | Total active power | W |
| \(Q\) | Total reactive power | var |
Method and standards
Delta load.
Where it is used
- Sizing feeders for line-to-line loads.
- Balancing single-phase loads across phases.
Common mistakes
- Adding current magnitudes instead of phasors.
- Using phase voltage across delta branches.
Assumptions and limits
- Balanced positive-sequence supply; linear branches.
References
- Phasor circuit analysis
Questions and answers
Why are line currents not √3 times the phase currents?
That relation holds only for balanced loads; with unequal branches each line current is a phasor difference of two different branch currents.
Where do unbalanced delta loads occur?
Single-phase loads such as welders, heaters and furnaces connected between lines.
What do the defaults represent?
Illustrative branches of 20 + j10, 30 and 15 − j10 Ω on a 415 V supply.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Hayt, Kemmerly and Durbin, Engineering Circuit Analysis, 8th ed. (McGraw-Hill, 2012)