Unbalanced Star Load: Neutral Shift (Millman) and Phase Voltages

Neutral displacement voltage of an unearthed star load with unequal resistive and reactive phase impedances on a balanced supply, by Millman's theorem.

Thermal power plantProcess steam and utilities

Inputs

Examples: Illustrative 10, 20, 40 ohm starBroken neutral, one heavy phaseMixed R-L-C star

Accepted: 1 to 1,000,000 V
Accepted: 0 to 1,000,000 Ω
Accepted: -1,000,000 to 1,000,000 Ω
Accepted: 0 to 1,000,000 Ω
Accepted: -1,000,000 to 1,000,000 Ω
Accepted: 0 to 1,000,000 Ω
Accepted: -1,000,000 to 1,000,000 Ω

Results

Millman: V_N = Σ(E_i/Z_i)/Σ(1/Z_i) for a star load with no neutral connection; each phase sees E_i − V_N. With a broken neutral, lightly loaded phases rise towards line voltage and damage equipment, which is why single-phase loads need a solid neutral.

Neutral shift voltage90.560V
Voltage across phase A156.86V
Voltage across phase B271.68V
Voltage across phase C313.71V

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 10, 20, 40 ohm star. The inputs, in the units selected above:

InputValue
Line voltage415.00 V
Phase A resistance10.000 Ω
Phase A reactance0 Ω
Phase B resistance20.000 Ω
Phase B reactance0 Ω
Phase C resistance40.000 Ω
Phase C reactance0 Ω

Applying the formula below gives:

ResultValue
Neutral shift voltage90.560 V
Voltage across phase A156.86 V
Voltage across phase B271.68 V
Voltage across phase C313.71 V

Open this example in the calculator and change any input.

Formula

\(V_N = \frac{\sum_iE_i/Z_i}{\sum_i1/Z_i}, \quad V_{i,load} = E_i - V_N\)

Variables

Symbol Meaning SI unit
\(V_{LL}\) Line voltage V
\(R_a\) Phase A resistance Ω
\(X_a\) Phase A reactance Ω
\(R_b\) Phase B resistance Ω
\(X_b\) Phase B reactance Ω
\(R_c\) Phase C resistance Ω
\(X_c\) Phase C reactance Ω
\(V_N\) Neutral shift voltage V
\(V_{a}\) Voltage across phase A V
\(V_b\) Voltage across phase B V
\(V_c\) Voltage across phase C V

Method and standards

Neutral shift.

Where it is used

  • Broken-neutral fault analysis.
  • Three-wire supply to unequal loads.

Common mistakes

  • Assuming phase voltages stay at 240 V without a neutral.
  • Using magnitudes instead of phasors.

Assumptions and limits

  • Balanced positive-sequence supply; linear loads.

References

  • Millman's theorem

Questions and answers

Why are broken neutrals dangerous?

Without the neutral, unequal loads shift the star point and some phases get far more than their rated voltage.

Does the phase sequence matter?

Yes with reactive loads: swapping two phases changes which phase sees the higher voltage.

What do the defaults represent?

An illustrative 415 V supply feeding an unearthed star of 10, 20 and 40 Ω resistive loads.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Hayt, Kemmerly and Durbin, Engineering Circuit Analysis, 8th ed. (McGraw-Hill, 2012)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.