Unbalanced Delta Load: Phase and Line Currents

Phase currents of an unbalanced delta-connected load with resistive and reactive branches on a balanced supply, the line currents and the total power.

Thermal power plantProcess steam and utilities

Inputs

Examples: Illustrative mixed delta at 415 VWelder on one branch only (others light)Balanced check 10 ohm

Accepted: 1 to 1,000,000 V
Accepted: 0 to 1,000,000 Ω
Accepted: -1,000,000 to 1,000,000 Ω
Accepted: 0 to 1,000,000 Ω
Accepted: -1,000,000 to 1,000,000 Ω
Accepted: 0 to 1,000,000 Ω
Accepted: -1,000,000 to 1,000,000 Ω

Results

Branch currents I_ab = V_ab/Z_ab etc.; line currents by Kirchhoff at each corner, I_A = I_ab − I_ca. With unequal branches the line currents differ and are not √3 times any branch current. Positive reactance is inductive, negative capacitive.

Line current A69.282A
Line current B69.282A
Line current C69.282A
Total active power48.000kW
Total reactive power-9.0949e-16kvar

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative mixed delta at 415 V. The inputs, in the units selected above:

InputValue
Line voltage415.00 V
Branch AB resistance20.000 Ω
Branch AB reactance10.000 Ω
Branch BC resistance30.000 Ω
Branch BC reactance0 Ω
Branch CA resistance15.000 Ω
Branch CA reactance-10.000 Ω

Applying the formula below gives:

ResultValue
Line current A41.579 A
Line current B23.803 A
Line current C26.082 A
Total active power20.579 kW
Total reactive power-1.8547 kvar

Open this example in the calculator and change any input.

Formula

\(I_{ab} = \frac{V_{ab}}{Z_{ab}}, \quad I_A = I_{ab} - I_{ca}, \quad S = \sum V_{xy}I_{xy}^*\)

Variables

Symbol Meaning SI unit
\(V_{LL}\) Line voltage V
\(R_{ab}\) Branch AB resistance Ω
\(X_{ab}\) Branch AB reactance Ω
\(R_{bc}\) Branch BC resistance Ω
\(X_{bc}\) Branch BC reactance Ω
\(R_{ca}\) Branch CA resistance Ω
\(X_{ca}\) Branch CA reactance Ω
\(I_A\) Line current A A
\(I_B\) Line current B A
\(I_C\) Line current C A
\(P\) Total active power W
\(Q\) Total reactive power var

Method and standards

Delta load.

Where it is used

  • Sizing feeders for line-to-line loads.
  • Balancing single-phase loads across phases.

Common mistakes

  • Adding current magnitudes instead of phasors.
  • Using phase voltage across delta branches.

Assumptions and limits

  • Balanced positive-sequence supply; linear branches.

References

  • Phasor circuit analysis

Questions and answers

Why are line currents not √3 times the phase currents?

That relation holds only for balanced loads; with unequal branches each line current is a phasor difference of two different branch currents.

Where do unbalanced delta loads occur?

Single-phase loads such as welders, heaters and furnaces connected between lines.

What do the defaults represent?

Illustrative branches of 20 + j10, 30 and 15 − j10 Ω on a 415 V supply.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Hayt, Kemmerly and Durbin, Engineering Circuit Analysis, 8th ed. (McGraw-Hill, 2012)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.