Worked example
Example: Illustrative 24 V relay coil with 470 ohm. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Coil supply voltage | 24.000 V |
| Coil resistance | 160.00 Ω |
| Coil inductance | 800.00 mH |
| Suppression resistor across the coil | 470.00 Ω |
| Drop-out current as a share of holding current | 15.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Coil current | 150.00 mA |
| Stored magnetic energy | 9.0000 mJ |
| Coil voltage spike with the resistor | 70.500 V |
| Voltage across the opening switch | 94.500 V |
| Release delay with a diode | 9.4856 ms |
| Release delay with the resistor | 2.4090 ms |
Open this example in the calculator and change any input.
Formula
\(I = \frac{V}{R_c}, \quad V_{spike} = IR_s, \quad t_r = \frac{L}{R_c + R_s}\ln\frac{I}{I_{do}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(V\) | Coil supply voltage | V |
| \(R_c\) | Coil resistance | Ω |
| \(L\) | Coil inductance | H |
| \(R_s\) | Suppression resistor across the coil | Ω |
| \(I_{do}/I\) | Drop-out current as a share of holding current | - |
| \(I\) | Coil current | A |
| \(E\) | Stored magnetic energy | J |
| \(V_{spike}\) | Coil voltage spike with the resistor | V |
| \(V_{sw}\) | Voltage across the opening switch | V |
| \(t_{r,diode}\) | Release delay with a diode | s |
| \(t_{r,R}\) | Release delay with the resistor | s |
Method and standards
Coil suppression.
Where it is used
- PLC output and transistor driver protection.
- Contactor drop-out timing.
Common mistakes
- Leaving inductive loads unsuppressed.
- Using diode suppression where fast release matters (e.g. brakes).
Assumptions and limits
- Constant inductance; ideal diode; drop-out at a fixed current.
References
- RL decay with clamping
Questions and answers
Why does a diode slow the relay?
It lets the coil current circulate and decay slowly, so the magnetic pull lasts longer.
How do I get fast release and a safe spike?
Use a resistor, a Zener plus diode or a TVS so the clamp voltage is higher but bounded.
What do the defaults represent?
An illustrative 24 V DC relay coil of 160 Ω and 0.8 H with a 470 Ω suppression resistor, dropping out at 15 % of holding current.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Hayt and Kemmerly, Engineering Circuit Analysis, 8th ed. (McGraw-Hill, 2012)