FireCADCalc

Capacitor Discharge Resistor for a Safe Voltage

Largest discharge resistor that brings a capacitor down to a safe voltage within a set time, with the time constant, stored energy and continuous resistor loss.

Inputs

Examples: Illustrative 400 uF DC link from 650 VPower factor capacitor 75 V in 3 minSmall supply 10 s

Accepted: 1E-6 to 10,000,000 µF
Accepted: 1 to 1,000,000 V
Accepted: 0.1 to 100,000 V
Accepted: 1E-6 to 100,000 s

Results

A capacitor discharging through R decays as V = V₀e^(−t/RC), so reaching V_s by time t needs R ≤ t/[C ln(V₀/V_s)]. A permanently connected resistor dissipates V₀²/R all the time, so choose the largest value that meets the time. Power factor capacitors are commonly required to fall to 75 V within 3 minutes, and DC bus capacitors in drives to a touch-safe level (about 50–60 V) within a stated time. Use resistors rated for the full voltage and the pulse energy.

Largest resistor that meets the time567.15kΩ
Time constant RC85.072s
Stored energy29.040J
Continuous loss at the initial voltage0.68272W

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 400 uF DC link from 650 V. The inputs, in the units selected above:

InputValue
Capacitance400.00 µF
Initial (peak) voltage650.00 V
Safe voltage50.000 V
Time allowed to reach the safe voltage60.000 s

Applying the formula below gives:

ResultValue
Largest resistor that meets the time58.481 kΩ
Time constant RC23.392 s
Stored energy84.500 J
Continuous loss at the initial voltage7.2246 W

Open this example in the calculator and change any input.

Formula

\(R_{max} = \frac{t}{C\ln(V_0/V_s)}, \quad E = \tfrac12CV_0^2\)

Variables

Symbol Meaning SI unit
\(C\) Capacitance F
\(V_0\) Initial (peak) voltage V
\(V_s\) Safe voltage V
\(t\) Time allowed to reach the safe voltage s
\(R_{max}\) Largest resistor that meets the time Ω
\(\tau\) Time constant RC s
\(E\) Stored energy J
\(P_R\) Continuous loss at the initial voltage W

Method and standards

Bleeder resistor.

Where it is used

  • Drive DC links, power factor capacitors and power supplies.
  • Safety interlock design.

Common mistakes

  • Using RMS instead of peak voltage.
  • Ignoring the resistor's voltage rating.

Assumptions and limits

  • Ideal capacitor and resistor; no other load on the capacitor.

References

  • RC discharge

Questions and answers

Why not use a very small resistor?

It would waste V₀²/R continuously and heat up; the bleeder only needs to meet the time.

What voltage should I use for AC capacitors?

The peak voltage, √2 times the RMS, because the capacitor can be left charged at the peak.

What do the defaults represent?

An illustrative 400 µF DC link at 650 V that must fall to 50 V within 60 s.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Hayt and Kemmerly, Engineering Circuit Analysis, 8th ed. (McGraw-Hill, 2012)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.