FireCADCalc

Pool Fire: Burning Rate, Flame Length and Heat Released

Burning rate of a liquid pool fire (Burgess), the mean flame length with wind (TNO), and the heat released, from the fuel's heats and boiling point.

Process steam and utilitiesDistillery and ethanolRefinery and petrochemicalChemical and fertiliserTank and drum

Inputs

Examples: 10 m hexane pool, 5 m/s wind20 m gasoline-like pool, calmPropane pool (boils below ambient)

Results

Burgess' correlation is for single-component liquids at ambient conditions and not for alcohols; tabulated large-pool burning rates are better where they exist (e.g. gasoline 0.055, hexane 0.074 kg/(m²·s) in TNO Table 6.5). Only part of the heat released is radiated (typically 15–35 %).

A screening estimate for training and early design, not a hazard or risk study.

Burning rate per area0.10869kg/(m²·s)
Characteristic wind velocity1.6439m/s
Scaled wind velocity (at least 1)1.8249
Mean flame length13.161m
Flame length to diameter2.6322
Heat released98.806MW

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 10 m hexane pool, 5 m/s wind. The inputs, in the units selected above:

InputValue
Pool diameter10.000 m
Heat of combustion44,600 kJ/kg
Heat of vaporisation at the boiling point336.00 kJ/kg
Liquid heat capacity2.2400 kJ/(kg·K)
Boiling point68.750 °C
Ambient temperature20.000 °C
Wind speed at 10 m5.0000 m/s
Air density1.2000 kg/m³

Applying the formula below gives:

ResultValue
Burning rate per area0.10018 kg/(m²·s)
Characteristic wind velocity2.0157 m/s
Scaled wind velocity (at least 1)2.4805
Mean flame length18.525 m
Flame length to diameter1.8525
Heat released350.92 MW

Open this example in the calculator and change any input.

Formula

\(m'' = \frac{0.001\,\Delta H_c}{\Delta H_v + C_p(T_b - T_a)}, \quad u_c = \left(\frac{g\,m''D}{\rho_{air}}\right)^{1/3}, \quad u^* = \max\left(\frac{u_w}{u_c}, 1\right)\)

\(\frac{L}{D} = 55\left(\frac{m''}{\rho_{air}\sqrt{gD}}\right)^{0.67}(u^*)^{-0.21}, \quad \dot Q = m''\frac{\pi D^2}{4}\Delta H_c\)

Variables

Symbol Meaning SI unit
\(D\) Pool diameter m
\(\Delta H_c\) Heat of combustion J/kg
\(\Delta H_v\) Heat of vaporisation at the boiling point J/kg
\(C_p\) Liquid heat capacity J/(kg·K)
\(T_b\) Boiling point K
\(T_a\) Ambient temperature K
\(u_w\) Wind speed at 10 m m/s
\(\rho_{air}\) Air density kg/m³
\(m''\) Burning rate per area kg/(m²·s)
\(u_c\) Characteristic wind velocity m/s
\(u^*\) Scaled wind velocity (at least 1) -
\(L\) Mean flame length m
\(L/D\) Flame length to diameter -
\(\dot Q\) Heat released W

Method and standards

TNO Yellow Book pool fire model: Burgess burning rate and the Thomas-type flame length with wind.

Where it is used

  • Tank and bund fire scenarios (screening).
  • Fire-water and spacing studies.

Common mistakes

  • Using it for alcohols.
  • Taking all heat released as radiated.

Assumptions and limits

  • Circular pool; single-component liquid.

References

  • TNO Yellow Book
  • Methods for the Calculation of Physical Effects
  • CPR 14E
  • 3rd ed. (2005)
  • ch. 6
  • §6.5.4
  • eqs. 6.12–6.14 and 6.67 (Burgess; Thomas)

Questions and answers

Why does the burning rate depend on the boiling point?

The flame must heat the liquid up to its boiling point and then vaporise it; fuels that need less heat per kilogram burn faster.

Does wind make the flame longer?

No: above the characteristic speed u_c the flame tilts and shortens, as the u*^(−0.21) term shows.

What do the defaults represent?

A 10 m hexane pool fire (ΔH_c 44.6 MJ/kg, boiling point 69 °C) in a 5 m/s wind.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.