Worked example
Example: 10 m hexane pool, 5 m/s wind. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Pool diameter | 10.000 m |
| Heat of combustion | 44,600 kJ/kg |
| Heat of vaporisation at the boiling point | 336.00 kJ/kg |
| Liquid heat capacity | 2.2400 kJ/(kg·K) |
| Boiling point | 68.750 °C |
| Ambient temperature | 20.000 °C |
| Wind speed at 10 m | 5.0000 m/s |
| Air density | 1.2000 kg/m³ |
Applying the formula below gives:
| Result | Value |
|---|---|
| Burning rate per area | 0.10018 kg/(m²·s) |
| Characteristic wind velocity | 2.0157 m/s |
| Scaled wind velocity (at least 1) | 2.4805 |
| Mean flame length | 18.525 m |
| Flame length to diameter | 1.8525 |
| Heat released | 350.92 MW |
Open this example in the calculator and change any input.
Formula
\(m'' = \frac{0.001\,\Delta H_c}{\Delta H_v + C_p(T_b - T_a)}, \quad u_c = \left(\frac{g\,m''D}{\rho_{air}}\right)^{1/3}, \quad u^* = \max\left(\frac{u_w}{u_c}, 1\right)\)
\(\frac{L}{D} = 55\left(\frac{m''}{\rho_{air}\sqrt{gD}}\right)^{0.67}(u^*)^{-0.21}, \quad \dot Q = m''\frac{\pi D^2}{4}\Delta H_c\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(D\) | Pool diameter | m |
| \(\Delta H_c\) | Heat of combustion | J/kg |
| \(\Delta H_v\) | Heat of vaporisation at the boiling point | J/kg |
| \(C_p\) | Liquid heat capacity | J/(kg·K) |
| \(T_b\) | Boiling point | K |
| \(T_a\) | Ambient temperature | K |
| \(u_w\) | Wind speed at 10 m | m/s |
| \(\rho_{air}\) | Air density | kg/m³ |
| \(m''\) | Burning rate per area | kg/(m²·s) |
| \(u_c\) | Characteristic wind velocity | m/s |
| \(u^*\) | Scaled wind velocity (at least 1) | - |
| \(L\) | Mean flame length | m |
| \(L/D\) | Flame length to diameter | - |
| \(\dot Q\) | Heat released | W |
Method and standards
TNO Yellow Book pool fire model: Burgess burning rate and the Thomas-type flame length with wind.
Where it is used
- Tank and bund fire scenarios (screening).
- Fire-water and spacing studies.
Common mistakes
- Using it for alcohols.
- Taking all heat released as radiated.
Assumptions and limits
- Circular pool; single-component liquid.
References
- TNO Yellow Book
- Methods for the Calculation of Physical Effects
- CPR 14E
- 3rd ed. (2005)
- ch. 6
- §6.5.4
- eqs. 6.12–6.14 and 6.67 (Burgess; Thomas)
Questions and answers
Why does the burning rate depend on the boiling point?
The flame must heat the liquid up to its boiling point and then vaporise it; fuels that need less heat per kilogram burn faster.
Does wind make the flame longer?
No: above the characteristic speed u_c the flame tilts and shortens, as the u*^(−0.21) term shows.
What do the defaults represent?
A 10 m hexane pool fire (ΔH_c 44.6 MJ/kg, boiling point 69 °C) in a 5 m/s wind.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.