FireCADCalc

Limiting Oxygen Concentration from LFL (Inerting Target)

Limiting oxygen concentration of a fuel from its lower flammability limit and stoichiometric oxygen (LOC = z·LFL), with an inerting target.

Distillery and ethanolRefinery and petrochemicalChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: Methane, LFL 5 %Ethanol, LFL 3.3 %

A fixed 2-point margin is a common screening figure. Inerting standards such as NFPA 69 set the margin by how the oxygen is monitored, in some cases as a percentage of the LOC; follow the edition you work to.

Results

Perry's notes this estimate is approximate; measured LOC values (ASTM E2079) govern. Screening estimate only, not a safety study or a basis for protective design.

Moles of O₂ per mole of fuel3.0000
Limiting oxygen concentration9.9000%
Maximum O₂ to operate at7.9000%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Methane, LFL 5 %. The inputs, in the units selected above:

InputValue
Lower flammability limit5.0000 %
Carbon atoms in the fuel1.0000 -
Hydrogen atoms4.0000 -
Oxygen atoms0 -
Safety margin below LOC (percentage points)2.0000 %

Applying the formula below gives:

ResultValue
Moles of O₂ per mole of fuel2.0000
Limiting oxygen concentration10.000 %
Maximum O₂ to operate at8.0000 %

Open this example in the calculator and change any input.

Formula

\(z = m + \frac{x}{4} - \frac{y}{2}\ (C_mH_xO_y), \quad LOC = z\cdot LFL\)

Variables

Symbol Meaning SI unit
\(LFL\) Lower flammability limit -
\(m\) Carbon atoms in the fuel -
\(x\) Hydrogen atoms -
\(y\) Oxygen atoms -
\(\Delta\) Safety margin below LOC (percentage points) -
\(z\) Moles of O₂ per mole of fuel -
\(LOC\) Limiting oxygen concentration -
\(O_{2,max}\) Maximum O₂ to operate at -

Method and standards

Perry's Eq. (23-8).

Where it is used

  • Inerting design screening.

Common mistakes

  • Using it instead of measured LOC.
  • No margin for analyser error.

Assumptions and limits

  • Approximate; measured data (ASTM E2079) govern. The estimate can be non-conservative for some fuels whose measured LOC is lower than z·LFL.
  • Only C, H and O atoms are handled; fuels with N, S or halogens need measured values.
  • The operating target subtracts a fixed margin in percentage points; inerting standards may set it as a percentage of the LOC depending on monitoring.

References

  • Perry's Chemical Engineers' Handbook
  • 9th ed. (McGraw-Hill, 2019)
  • sec. 23
  • Eq. (23-8): LOC = z·LFL

Questions and answers

What is LOC?

The oxygen concentration below which no mixture of the fuel with air and inert can burn.

Why z·LFL?

At the LFL the fuel just burns; the oxygen it uses there is z times the LFL.

What does methane give?

LFL 5 %, z = 2: LOC about 10 % O₂ (measured about 12 % with nitrogen).

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators