FireCADCalc

Flammability Limits: Estimate and Effect of Temperature and Pressure

Lower and upper flammability limits of a CxHyOz fuel from stoichiometry (Jones), and the shift of the limits with temperature and of the upper limit with pressure.

Process steam and utilitiesDistillery and ethanolRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: Propane at 100 °C and 2 MPaEthanol at 50 °C, 1 atmHexane at 25 °C, 6.3 MPa

Results

Jones' stoichiometric estimate (LFL = 0.55 C_st, UFL = 3.5 C_st) suits hydrocarbon vapours; measured limits are always better. The temperature and pressure formulas are approximate and hold only over limited ranges; the LFL changes little with pressure.

A screening estimate for training and early design, not a hazard or risk study.

Stoichiometric fuel concentration in air2.1578%
Lower flammability limit at 25 °C, 1 atm1.1868%
Upper flammability limit at 25 °C, 1 atm7.5523%
LFL at temperature T1.1868%
UFL at temperature T7.5523%
UFL at pressure P (25 °C)44.620%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Propane at 100 °C and 2 MPa. The inputs, in the units selected above:

InputValue
Carbon atoms in the fuel molecule3.0000 -
Hydrogen atoms8.0000 -
Oxygen atoms0 -
Net heat of combustion (for the temperature effect)2,043.5 kJ/mol
Temperature100.00 °C
Pressure (absolute)2,000.0 kPa

Applying the formula below gives:

ResultValue
Stoichiometric fuel concentration in air4.0217 %
Lower flammability limit at 25 °C, 1 atm2.2119 %
Upper flammability limit at 25 °C, 1 atm14.076 %
LFL at temperature T2.0968 %
UFL at temperature T14.191 %
UFL at pressure P (25 °C)40.877 %

Open this example in the calculator and change any input.

Formula

\(C_{st} = \frac{100}{1 + 4.773z},\ z = m + \frac{x}{4} - \frac{y}{2}, \quad LFL = 0.55C_{st}, \quad UFL = 3.50C_{st}\)

\(LFL_T = LFL_{25} - \frac{0.75}{\Delta H_c}(T - 25), \quad UFL_T = UFL_{25} + \frac{0.75}{\Delta H_c}(T - 25), \quad UFL_P = UFL + 20.6(\log P + 1)\)

Variables

Symbol Meaning SI unit
\(m\) Carbon atoms in the fuel molecule -
\(x\) Hydrogen atoms -
\(y\) Oxygen atoms -
\(\Delta H_c\) Net heat of combustion (for the temperature effect) J/mol
\(T\) Temperature K
\(P\) Pressure (absolute) Pa
\(C_{st}\) Stoichiometric fuel concentration in air -
\(LFL\) Lower flammability limit at 25 °C, 1 atm -
\(UFL\) Upper flammability limit at 25 °C, 1 atm -
\(LFL_T\) LFL at temperature T -
\(UFL_T\) UFL at temperature T -
\(UFL_P\) UFL at pressure P (25 °C) -

Method and standards

Jones' correlation with the stoichiometric concentration; temperature effect from Zabetakis (ΔH_c in kcal/mol, T in °C, limits in volume %); UFL with pressure in MPa absolute.

Where it is used

  • Inerting and purge design.
  • Area classification inputs and safe operating windows.

Common mistakes

  • Using gross heat of combustion.
  • Applying the pressure formula to the LFL.

Assumptions and limits

  • Hydrocarbon vapours; approximate.

References

  • Crowl and Louvar
  • Chemical Process Safety: Fundamentals with Applications
  • 2nd ed. (Prentice Hall, 2002)
  • ch. 6
  • eqs. 6-4 to 6-11 (Jones; Zabetakis)

Questions and answers

Why does the range widen with temperature?

A warmer mixture needs less heat from the reaction to keep a flame going, so leaner and richer mixtures burn.

Does pressure change the LFL?

Very little above about 50 mmHg; the UFL rises markedly with pressure.

What do the defaults represent?

Propane (C₃H₈, ΔH_c 2,043.5 kJ/mol) at 100 °C, and its upper limit at 20 bar.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.