Worked example
Example: 10 t LPG at 20 bar, 200 m. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Mass of flammable material | 10,000 kg |
| Heat of combustion | 46,000 kJ/kg |
| Heat of vaporisation | 426.00 kJ/kg |
| Specific heat of the vapour | 2.0000 kJ/(kg·K) |
| Vapour pressure in the vessel at failure (absolute) | 2,000.0 kPa |
| Ground distance from below the fireball to the target | 200.00 m |
| Partial pressure of water vapour in air | 2.0000 kPa |
Applying the formula below gives:
| Result | Value |
|---|---|
| Fireball radius | 64.646 m |
| Fireball duration | 9.3420 s |
| Height of the fireball centre | 129.29 m |
| Fraction of heat radiated | 33.745 % |
| Surface emissive power | 290.08 kW/m² |
| Atmospheric transmissivity | 64.080 % |
| Heat flux at the target | 13.697 kW/m² |
Open this example in the calculator and change any input.
Formula
\(r_{fb} = 3.24m^{0.325}, \quad t = 0.852m^{0.26}, \quad H = 2r_{fb}, \quad F_s = 0.00325P_{sv}^{0.32}\)
\(SEP = \frac{(\Delta H_c - \Delta H_v - C_p\Delta T)\,m\,F_s}{4\pi r_{fb}^2t}, \quad q = SEP\left(\frac{r_{fb}}{X}\right)^2\tau_a, \quad \tau_a = 2.02(p_wx)^{-0.09}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(m\) | Mass of flammable material | kg |
| \(\Delta H_c\) | Heat of combustion | J/kg |
| \(\Delta H_v\) | Heat of vaporisation | J/kg |
| \(C_p\) | Specific heat of the vapour | J/(kg·K) |
| \(P_{sv}\) | Vapour pressure in the vessel at failure (absolute) | Pa |
| \(x_{bleve}\) | Ground distance from below the fireball to the target | m |
| \(p_w\) | Partial pressure of water vapour in air | Pa |
| \(r_{fb}\) | Fireball radius | m |
| \(t\) | Fireball duration | s |
| \(H_{bleve}\) | Height of the fireball centre | m |
| \(F_s\) | Fraction of heat radiated | - |
| \(SEP\) | Surface emissive power | W/m² |
| \(\tau_a\) | Atmospheric transmissivity | - |
| \(q\) | Heat flux at the target | W/m² |
Method and standards
TNO Yellow Book fireball model (ΔT = 1,700 K between flame and ambient; X from the fireball centre, x = X − r from its surface).
Where it is used
- LPG storage and road tanker siting (screening).
- Emergency planning distances.
Common mistakes
- Using the whole vessel inventory when only part takes part.
- Ignoring the fireball's lift-off height.
Assumptions and limits
- Uniform SEP; spherical fireball after lift-off.
References
- TNO Yellow Book
- Methods for the Calculation of Physical Effects
- CPR 14E
- 3rd ed. (2005)
- ch. 6
- §6.5.7
- eqs. 6.21
- 6.22
- 6.29 and 6.90–6.96
Questions and answers
What causes a BLEVE?
A vessel of liquefied gas fails, often when fire heats the shell above the liquid; the liquid flashes and the released fuel burns as a fireball.
How dangerous is the heat?
Around 5 kW/m² causes pain within about 20 s; tens of kW/m² for the fireball duration can be fatal (see the burn probit).
What do the defaults represent?
10 t of LPG at 20 bar in the vessel, a target 200 m away, humid air (2 kPa water vapour).
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.