Worked example
Example: Illustrative 600 kg/h freezer. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Mix flow | 600.00 kg/h |
| Mix inlet temperature | 4.0000 °C |
| Initial freezing point of the mix | -2.5000 °C |
| Draw temperature | -5.5000 °C |
| Water content of the mix | 62.000 % |
| Share of the water frozen at draw | 50.000 % |
| Specific heat of the unfrozen mix | 3.3000 kJ/(kg·K) |
| Specific heat of the partly frozen mix | 2.5000 kJ/(kg·K) |
| Dasher and friction heat as a share of the product heat | 15.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Sensible heat above freezing | 21.450 kJ/kg |
| Latent heat of the ice formed | 103.42 kJ/kg |
| Sensible heat below freezing | 7.5000 kJ/kg |
| Refrigeration load | 25.370 kW |
| Load in tons of refrigeration | 7.2139 TR |
Open this example in the calculator and change any input.
Formula
\(\dot Q = \dot m\left[c_l(T_{in} - T_{fp}) + x_w f_i L_f + c_f(T_{fp} - T_d)\right](1 + f_d)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot m\) | Mix flow | kg/s |
| \(T_{in}\) | Mix inlet temperature | K |
| \(T_{fp}\) | Initial freezing point of the mix | K |
| \(T_{d}\) | Draw temperature | K |
| \(x_w\) | Water content of the mix | - |
| \(f_i\) | Share of the water frozen at draw | - |
| \(c_l\) | Specific heat of the unfrozen mix | J/(kg·K) |
| \(c_f\) | Specific heat of the partly frozen mix | J/(kg·K) |
| \(f_d\) | Dasher and friction heat as a share of the product heat | - |
| \(q_s\) | Sensible heat above freezing | J/kg |
| \(q_l\) | Latent heat of the ice formed | J/kg |
| \(q_f\) | Sensible heat below freezing | J/kg |
| \(\dot Q\) | Refrigeration load | W |
| \(\dot Q_{TR}\) | Load in tons of refrigeration | W |
Method and standards
Freezer load.
Where it is used
- Ice cream plant refrigeration design.
- Checking freezer capacity.
Common mistakes
- Ignoring dasher heat.
- Freezing all the water in the freezer.
Assumptions and limits
- Steady flow; mean specific heats.
References
- Refrigeration load of continuous ice cream freezing
- Tetra Pak
- Dairy Processing Handbook (Tetra Pak Processing Systems, Lund)
Questions and answers
How much refrigeration does a 600 kg/h freezer need?
About 25 kW (7 TR) with the defaults.
Why only half the water frozen?
At −5 to −6 °C the remaining water holds enough dissolved sugar to stay liquid; hardening freezes more.
What do the defaults represent?
An illustrative 600 kg/h of mix from 4 °C, freezing point −2.5 °C, drawn at −5.5 °C with half its water frozen.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.