Worked example
Example: 10 t meat 20 → −18 °C in 24 h. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Product | 10,000 kg |
| Specific heat above freezing | 3.6000 kJ/(kg·K) |
| Specific heat below freezing | 1.8000 kJ/(kg·K) |
| Water that freezes (share of mass) | 70.000 % |
| Initial temperature | 20.000 °C |
| Initial freezing point | -2.0000 °C |
| Final temperature | -18.000 °C |
| Pull-down time | 24.000 h |
Applying the formula below gives:
| Result | Value |
|---|---|
| Sensible heat above freezing | 792.00 MJ |
| Latent heat | 2,334.8 MJ |
| Sensible heat below freezing | 288.00 MJ |
| Total | 3,414.8 MJ |
| Average refrigeration load | 39.524 kW |
Open this example in the calculator and change any input.
Formula
\(Q_1 = Mc_u\max\left[T_1 - \max(T_f, T_2), 0\right], \quad Q_2 = Mw_f\lambda_f\ (T_2 < T_f), \quad Q_3 = Mc_f\max\left[\min(T_f, T_1) - T_2, 0\right]\)
\(Q = Q_1 + Q_2 + Q_3, \quad \dot Q = \frac{Q}{t}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(M\) | Product | kg |
| \(c_u\) | Specific heat above freezing | J/(kg·K) |
| \(c_f\) | Specific heat below freezing | J/(kg·K) |
| \(w_f\) | Water that freezes (share of mass) | - |
| \(T_1\) | Initial temperature | K |
| \(T_f\) | Initial freezing point | K |
| \(T_2\) | Final temperature | K |
| \(t\) | Pull-down time | s |
| \(Q_1\) | Sensible heat above freezing | J |
| \(Q_2\) | Latent heat | J |
| \(Q_3\) | Sensible heat below freezing | J |
| \(Q\) | Total | J |
| \(\dot Q\) | Average refrigeration load | W |
| \(\lambda_f\) | Latent heat of fusion of ice, 333 550 | J/kg |
Method and standards
Sensible and latent heat balance.
Where it is used
- Blast freezer and cold store sizing.
Common mistakes
- Ignoring the latent heat.
- Using total water as frozen water.
Assumptions and limits
- Freezing at one temperature.
- A product entered at or below its freezing point is taken as unfrozen (supercooled) and the full latent heat is counted; for product already frozen, Q is high by M w_f λ_f.
- The load is an average over the pull-down time; the peak at the start is higher.
References
- Mass and energy balances (definitions); latent heat of fusion of ice 333.55 kJ/kg
Questions and answers
Why is latent heat so large?
Freezing water takes 334 kJ/kg, as much as cooling water by 80 K.
Is all the water frozen?
No; some stays unfrozen at storage temperature, so w_f is less than the total water.
Why a lower specific heat below freezing?
Ice has about half the specific heat of water.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.