CIP Heating: Energy and Time to Heat Detergent

Energy and steam to heat CIP detergent and rinse tanks, and the time to heat with a given heater duty, for one cleaning cycle.

Food, dairy and textile

Inputs

Examples: 5 m3 caustic 15 → 75 °C, 200 kWAcid tank 3 m3 to 65 °C

Results

Recovering and reusing hot detergent (instead of single-use) cuts CIP heat by more than half.

Energy per cycle343.33kWh
Heating time103.00min
Steam per cycle580.28kg
Steam per day1,740.8kg

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 5 m3 caustic 15 → 75 °C, 200 kW. The inputs, in the units selected above:

InputValue
Tank solution volume5.0000 m³
Solution density1,030.0 kg/m³
Initial temperature15.000 °C
Cleaning temperature75.000 °C
Heater duty200.00 kW
Cycles per day3.0000 -
Steam latent heat2,130.0 kJ/kg

Applying the formula below gives:

ResultValue
Energy per cycle343.33 kWh
Heating time103.00 min
Steam per cycle580.28 kg
Steam per day1,740.8 kg

Open this example in the calculator and change any input.

Formula

\(E = V\rho c(T_2 - T_1), \quad t = \frac{E}{\dot Q}, \quad m_s = \frac{E}{h_{fg}}\)

Variables

Symbol Meaning SI unit
\(V\) Tank solution volume m³
\(\rho\) Solution density kg/m³
\(T_1\) Initial temperature K
\(T_2\) Cleaning temperature K
\(\dot Q\) Heater duty W
\(n\) Cycles per day -
\(h_{fg}\) Steam latent heat J/kg
\(E\) Energy per cycle J
\(t\) Heating time s
\(m_s\) Steam per cycle kg
\(m_d\) Steam per day kg

Method and standards

Sensible heat with c = 4.0 kJ/(kg·K).

Where it is used

  • CIP system design.
  • Steam and energy audits.

Common mistakes

  • Ignoring circuit volume.
  • Counting single-use tanks as recovered.

Assumptions and limits

  • No heat loss during heating.

References

  • Mass and energy balances (definitions); solution specific heat taken as 4.0 kJ/(kg·K)

Questions and answers

What temperature for caustic CIP?

70–80 °C for dairy; acid at 60–70 °C.

Is pipe heat counted?

No: add circuit warm-up and losses for a full cycle.

Why reuse detergent?

The tank is reheated from 50–60 °C instead of cold water.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.