Worked example
Example: 1.5 t/h furnace oil 40 to 110 °C, 10 % loss, 7 bar(a) steam. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Oil flow | 1,500.0 kg/h |
| Mean specific heat of the oil | 1.9500 kJ/(kg·K) |
| Oil temperature in | 40.000 °C |
| Oil temperature out (atomising or pumping) | 110.00 °C |
| Heat-loss allowance | 10.000 % |
| Heating steam pressure (saturated) | 5.9867 bar g |
Applying the formula below gives:
| Result | Value |
|---|---|
| Heater duty | 62.562 kW |
| Steam consumption | 109.04 kg/h |
| Steam saturation temperature | 164.95 °C |
Open this example in the calculator and change any input.
Formula
\(\dot Q = \dot m_o\,c_p\,(T_2 - T_1)\,(1 + \lambda) \qquad \dot m_s = \frac{\dot Q}{h_{fg}(p_s)}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot m_o\) | oil flow | kg/s |
| \(c_p\) | mean specific heat of the oil | J/(kg·K) |
| \(T_1\) | oil temperature in | K |
| \(T_2\) | oil temperature out | K |
| \(\lambda\) | heat-loss allowance | – |
| \(p_s\) | heating steam pressure (absolute in SI; shown as gauge) | Pa |
| \(\dot Q\) | heater duty | W |
| \(\dot m_s\) | steam consumption | kg/s |
| \(T_{sat}\) | steam saturation temperature | K |
| \(h_{fg}\) | latent heat at \(p_s\) (IF97) | J/kg |
Method and standards
Energy balance of the oil; steam condenses at saturation and leaves as saturated condensate (FireCAD IAPWS-IF97).
Where it is used
- Sizing oil preheaters for burners.
- Steam budgets of oil-fired boiler houses.
- Choosing heating steam pressure.
Common mistakes
- Using too low a steam pressure: the oil outlet must be well below the steam's saturation temperature.
- Forgetting the recirculation flow back to the tank.
- Using the specific heat of water.
Assumptions and limits
- Condensate leaves saturated (no subcooling); constant specific heat.
- The heat-loss allowance multiplies the oil duty; its 10 % default is a starting value, not a published one.
- The steam pressure is shown as gauge; the 15 K approach warning is a FireCAD rule of thumb.
References
- IAPWS R7-97(2012) IF97
- first law of thermodynamics
Questions and answers
How much steam does a fuel oil heater use?
The oil's heat gain divided by the steam's latent heat. 1.5 t/h of furnace oil from 40 to 110 °C at 1.95 kJ/(kg·K) with a 10 % loss allowance takes 62.6 kW, about 109 kg/h of steam at 7 bar(a).
What temperature does the oil need?
The temperature that brings it to the burner's atomising viscosity; the viscosity calculator finds it from two known points.
Electric or steam heating?
Electric heaters start a cold plant; steam heaters run it once steam is available, at a fraction of the cost.
Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.