Worked example
Example: 20 MW on chips, 35 %, 15 days. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Boiler fuel heat input (NCV basis, not GCV) | 20.000 MW |
| Operating hours per day | 24.000 h |
| Days of storage | 15.000 - |
| Net calorific value, dry basis | 18.000 MJ/kg |
| Moisture, wet basis | 35.000 % |
| Bulk density as stored (wet) | 250.00 kg/m³ |
Applying the formula below gives:
| Result | Value |
|---|---|
| Net calorific value as received | 10.845 MJ/kg |
| Fuel flow | 6.6388 t/h |
| Fuel to store | 2,390.0 t |
| Storage volume | 9,559.8 m³ |
| Energy density of the stored fuel (NCV) | 753.15 kWh/m³ |
Open this example in the calculator and change any input.
Formula
\(NCV = NCV_d(1 - w) - h_{fg,25}\,w, \quad \dot m_f = \frac{Q_{in}}{NCV}\)
\(M = \dot m_f\,h_d\,n, \quad V = \frac{M}{\rho_b}, \quad e_V = \rho_b\,NCV\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q_{in}\) | Boiler fuel heat input (NCV basis) | W |
| \(h_d\) | Operating hours per day | s |
| \(n\) | Days of storage | - |
| \(NCV_d\) | Net calorific value, dry basis | J/kg |
| \(w\) | Moisture, wet basis | - |
| \(\rho_b\) | Bulk density as stored (wet) | kg/m³ |
| \(NCV\) | Net calorific value as received | J/kg |
| \(\dot m_f\) | Fuel flow | kg/s |
| \(M\) | Fuel to store | kg |
| \(V\) | Storage volume | m³ |
| \(e_V\) | Energy density of the stored fuel (NCV basis) | J/m³ |
| \(h_{fg,25}\) | latent heat of water at 25 °C (IAPWS-IF97), 2.442 | MJ/kg |
Method and standards
Mass and energy balance.
Where it is used
- Biomass boiler fuel yards.
- Seasonal fuel stocking.
Common mistakes
- Using dry-basis NCV for wet fuel.
- Ignoring compaction and settling.
Assumptions and limits
- Uniform moisture.
- The heat input is on the NCV basis. Boiler ratings are often on GCV; entering a GCV-basis input here understates the fuel flow and the storage.
References
- Moisture correction of calorific value (definitions; latent heat 2.442 MJ/kg at 25 °C from IAPWS-IF97)
Questions and answers
Why does moisture matter so much?
Wet fuel carries less heat per tonne and needs some of it to evaporate its own water; at 50 % moisture a fuel gives well under half its dry heat.
What bulk densities are typical?
Rice husk 100–130 kg/m³, wood chips 200–350, bagasse 120–160, pellets 600–700.
What do the defaults give?
20 MW input on chips at 35 % moisture (NCV 10.8 MJ/kg): about 6.7 t/h, 2,400 t and 9,600 m³ for 15 days.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.