Worked example
Example: 150 t bed + 100 t refractory to 600 °C. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Bed material | 150,000 kg |
| Bed specific heat | 0.84000 kJ/(kg·K) |
| Refractory heated | 100,000 kg |
| Refractory specific heat | 1.0000 kJ/(kg·K) |
| Initial temperature | 30.000 °C |
| Ignition temperature for coal | 600.00 °C |
| Start-up burner heat transfer efficiency | 50.000 % |
| Start-up fuel LHV | 42.000 MJ/kg |
| Heating time | 6.0000 h |
Applying the formula below gives:
| Result | Value |
|---|---|
| Heat to the bed and refractory | 128.82 GJ |
| Start-up fuel | 6.1343 t |
| Average fuel rate | 1,022.4 kg/h |
Open this example in the calculator and change any input.
Formula
\(Q = (M_bc_b + M_rc_r)(T_2 - T_1), \quad M_f = \frac{Q}{\eta_bLHV}, \quad \dot M_f = \frac{M_f}{t}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(M_b\) | Bed material | kg |
| \(c_b\) | Bed specific heat | J/(kg·K) |
| \(M_r\) | Refractory heated | kg |
| \(c_r\) | Refractory specific heat | J/(kg·K) |
| \(T_1\) | Initial temperature | K |
| \(T_2\) | Ignition temperature for coal | K |
| \(\eta_b\) | Start-up burner heat transfer efficiency | - |
| \(LHV\) | Start-up fuel LHV | J/kg |
| \(t\) | Heating time | s |
| \(Q\) | Heat to the bed and refractory | J |
| \(M_f\) | Start-up fuel | kg |
| \(\dot M_f\) | Average fuel rate | kg/s |
Method and standards
Sensible heat balance.
Where it is used
- Start-up fuel budgets.
Common mistakes
- Ignoring refractory.
- Assuming all burner heat reaches the bed.
Assumptions and limits
- Uniform final temperature: the bed and the refractory are both taken to reach the ignition temperature.
- Heat taken by the water walls, drum water and steam during the heat-up is not counted separately; it is folded into the burner heat transfer efficiency you enter.
References
- Basu
- Circulating Fluidized Bed Boilers: Design
- Operation and Maintenance (Springer, 2015)
- ch. 11 (start-up: bed heated by start-up burners to coal ignition temperature)
- Sensible heat balance
Questions and answers
To what temperature?
Bituminous coal is fed at about 500–600 °C bed temperature; low-volatile fuels need more.
Why is efficiency so low?
Much burner heat leaves with the flue gas while the bed and walls are cold.
Why count refractory?
Cyclones and loop seals carry large refractory masses that must be heated slowly.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.