CFBC Solids Circulation Rate and Circulation Ratio

Solids circulation rate of a circulating fluidised bed boiler from the riser solids flux, the circulation ratio to fuel, and the heat the returning solids carry.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationPulp and paperFood, dairy and textileBoiler

Inputs

Examples: 30 m² riser, 10 kg/(m²·s), 20 t/h fuel, solids cool 50 K45 m², 15 kg/(m²·s), 35 t/h, external heat exchanger to 650 °C20 m², 5 kg/(m²·s), 12 t/h, no cooling

From a loop-seal or pressure-profile measurement, or the boiler maker's design.
Lower than the furnace when an external heat exchanger cools the returning solids; equal otherwise.

Results

Solids circulation rate360.00t/h
Circulation ratio (solids per kg fuel)30.000kg/kg
Heat given up by the circulating solids0kW

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 30 m² riser, 10 kg/(m²·s), 20 t/h fuel, solids cool 50 K. The inputs, in the units selected above:

InputValue
Riser (furnace) cross-section30.000 m²
Net solids flux up the riser10.000 kg/(m²·s)
Fuel firing rate20.000 t/h
Specific heat of the solids0.83736 kJ/(kg·K)
Solids temperature leaving the furnace870.00 °C
Solids temperature returning to the furnace820.00 °C

Applying the formula below gives:

ResultValue
Solids circulation rate1,080.0 t/h
Circulation ratio (solids per kg fuel)54.000 kg/kg
Heat given up by the circulating solids12,560 kW

Open this example in the calculator and change any input.

Formula

\(\dot m_s = G_s A_r\)

\(\dot m_s / \dot m_f\)

\(Q_s = \dot m_s c_s (T_1 - T_2)\)

Variables

Symbol Meaning SI unit
\(A_r\) riser cross-section m²
\(G_s\) net solids flux up the riser kg/(m²·s)
\(\dot m_f\) fuel firing rate kg/s
\(c_s\) specific heat of the solids J/(kg·K)
\(T_1\) solids temperature leaving the furnace K
\(T_2\) solids temperature returning K
\(\dot m_s\) solids circulation rate kg/s
\(\dot m_s / \dot m_f\) circulation ratio kg/kg
\(Q_s\) heat given up by the solids W

Method and standards

The circulation rate is the net upward solids flux times the riser cross-section; the ratio to fuel is the usual design figure. The heat the solids give up between leaving the furnace and returning (in an external heat exchanger, or none) is circulation rate times specific heat times temperature drop. Default solids specific heat is FireCAD's ash value, 0.2 Btu/(lb·°F).

Where it is used

  • Checking a CFBC's circulation against the design.
  • Estimating external heat exchanger duty.
  • Explaining furnace temperature profiles.

Common mistakes

  • Using the gross upward flux instead of the net flux (part of the solids fall back down the walls).
  • Mixing kg/(m²·s) and t/(m²·h).
  • Using the bed area of the lower furnace instead of the riser cross-section.

Assumptions and limits

  • Net solids flux is an input, from measurement or design.
  • Mean specific heat of the solids.
  • Steady circulation.

References

  • Mass and heat balance on the solids loop

Questions and answers

What is a typical CFBC circulation ratio?

Tens of kg of solids per kg of fuel. A 30 m² riser at 10 kg/(m²·s) circulates 300 kg/s, 54 times the 20 t/h fuel rate.

How is the solids flux found on a running boiler?

From the pressure profile up the riser, from a loop-seal measurement, or from a heat balance across an external heat exchanger.

Why does circulation matter?

The circulating solids carry heat to the walls and the external heat exchanger and keep the furnace temperature even; too little circulation lets the bottom run hot.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.