Worked example
Example: 3000 kg/s, 41 to 32 °C, 5 cycles. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Circulating water flow | 1.0800e+07 kg/h |
| Hot water temperature | 41.000 °C |
| Cold water temperature | 32.000 °C |
| Share of heat removed by evaporation | 85.000 % |
| Cycles of concentration | 5.0000 - |
| Drift loss, share of circulating flow | 0.020000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Make-up water | 178,751 kg/h |
| Evaporation loss | 143,001 kg/h |
| Blowdown | 33,590 kg/h |
| Drift loss | 2,160.0 kg/h |
| Heat rejected | 112.83 MW |
Open this example in the calculator and change any input.
Formula
\(\dot Q = L\,\left[h(T_{hot}) - h(T_{cold})\right] \qquad E = \frac{f\,\dot Q}{h_{fg}(T_m)} \qquad D = d\,L\)
\(B = \frac{E}{C - 1} - D \qquad M = E + D + B\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(L\) | circulating water flow | kg/s |
| \(T_{hot}\) | hot water temperature | K |
| \(T_{cold}\) | cold water temperature | K |
| \(T_m\) | mean water temperature | K |
| \(f\) | share of heat removed by evaporation | – |
| \(C\) | cycles of concentration | – |
| \(d\) | drift as a share of circulating flow | – |
| \(M\) | make-up water | kg/s |
| \(E\) | evaporation loss | kg/s |
| \(B\) | blowdown | kg/s |
| \(D\) | drift loss | kg/s |
| \(\dot Q\) | heat rejected | W |
| \(h\), \(h_{fg}\) | water enthalpy and latent heat | J/kg |
Method and standards
Mass balance of the tower water and a dissolved-solids balance (make-up solids leave with blowdown and drift); evaporation from the heat removed by evaporation and the latent heat at the mean water temperature (FireCAD IAPWS-IF97).
Where it is used
- Water budgets for power, refinery and chemical plants.
- Setting blowdown for a chosen cycles of concentration.
- Valuing better treatment that allows higher cycles.
Common mistakes
- Counting drift as part of evaporation.
- Using the same evaporation share in winter and summer.
- Forgetting that drift also removes dissolved solids, so the blowdown valve may need to open less.
Assumptions and limits
- Steady state; all water losses are evaporation, drift and blowdown (no leaks).
- If drift alone exceeds the blowdown the cycles need, the blowdown is shown as zero and the cycles actually reached are lower; a warning gives them.
- Drift here is a share of circulating flow; the cycles-from-chemistry calculator takes it as a share of evaporation and takes all the heat as leaving by evaporation (\(f = 1\)).
References
- IAPWS R7-97(2012) IF97
- cooling tower mass balance (evaporation, drift, blowdown)
Questions and answers
How much make-up water does a cooling tower need?
Evaporation plus drift plus blowdown. 3000 kg/s cooled from 41 to 32 °C evaporates about 39.7 kg/s; at 5 cycles the blowdown is 9.3 kg/s and the make-up 49.7 kg/s, about 179 m³/h at roughly 1000 kg/m³.
What are cycles of concentration?
How many times the dissolved solids in the circulating water exceed those in the make-up. Higher cycles cut blowdown and make-up, but raise scaling risk; water treatment sets the limit.
Where does the 0.00085 rule come from?
About 85 % of the heat leaves by evaporation, and evaporating water takes about 1000 Btu/lb, so evaporation ≈ 0.00085 × flow × range in °F. This calculator uses the latent heat itself, with the share as an input.
Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.