Air-Cooled Condenser (ACC) Duty and Air Flow

Heat load of an air-cooled steam condenser and the air flow it needs from the exhaust steam flow, dryness, condenser pressure and air temperature rise, with the ITD.

Thermal power plantSugar mill and cogenerationChemical and fertiliserIAPWS-IF97 (water and steam)Condenser and cooling towerFan and blower

Inputs

Examples: 20 t/h at 0.2 bar(a), 92 % dry, air 35 to 52 °C100 t/h at 0.15 bar(a), 90 % dry, air 30 to 46 °C8 t/h at 0.25 bar(a), 94 % dry, air 40 to 56 °C, 600 m site

Results

Condenser heat load59.309MW
Air mass flow (dry air)1.3272e+07kg/h
Air volume flow at ambient (dry air)1.1549e+07m³/h
Initial temperature difference23.970K
Condensing temperature53.970°C

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 20 t/h at 0.2 bar(a), 92 % dry, air 35 to 52 °C. The inputs, in the units selected above:

InputValue
Exhaust steam flow20,000 kg/h
Exhaust steam dryness fraction92.000 %
Condenser pressure (absolute)20.000 kPa
Ambient air temperature35.000 °C
Air temperature leaving the bundles52.000 °C
Atmospheric pressure1.0132 bar

Applying the formula below gives:

ResultValue
Condenser heat load12.050 MW
Air mass flow (dry air)2,536,928 kg/h
Air volume flow at ambient (dry air)2,214,619 m³/h
Initial temperature difference25.059 K
Condensing temperature60.059 °C

Open this example in the calculator and change any input.

Formula

\(\dot Q = \dot m_s\,\left[h(p_c, x) - h_f(p_c)\right] \qquad \dot m_a = \frac{\dot Q}{h_a(T_{a,2}) - h_a(T_{a,1})}\)

\(\dot V_a = \frac{\dot m_a}{\rho_a},\quad \rho_a = \frac{p_{atm}\,M_{da}}{R\,T_{a,1}} \qquad ITD = T_{sat} - T_{a,1}\)

Variables

Symbol Meaning SI unit
\(\dot m_s\) exhaust steam flow kg/s
\(x\) exhaust steam dryness –
\(p_c\) condenser pressure, absolute Pa
\(T_{a,1}\) ambient air temperature K
\(T_{a,2}\) air temperature leaving the bundles K
\(p_{atm}\) atmospheric pressure Pa
\(\dot Q\) condenser heat load W
\(\dot m_a\) air mass flow kg/s
\(\dot V_a\) air volume flow at ambient m³/s
\(ITD\) initial temperature difference K
\(T_{sat}\) condensing temperature K
\(h\), \(h_f\) steam and saturated liquid enthalpy J/kg
\(h_a\) dry air enthalpy (Shomate) J/kg
\(\rho_a\) air density at ambient kg/m³
\(M_{da}\) molar mass of dry air kg/kmol
\(R\) universal gas constant J/(kmol·K)

Method and standards

Steam-side energy balance with FireCAD's IAPWS-IF97; air-side enthalpy from NIST Shomate heat capacities of dry air; air density by the ideal-gas law at ambient.

Where it is used

  • Sizing ACCs and their fans for plants without enough water.
  • Checking summer back pressure of an existing ACC.
  • Comparing wet and dry cooling at the concept stage.

Common mistakes

  • Designing on the average temperature instead of the hot-day temperature.
  • Ignoring hot-air recirculation, which raises the effective inlet temperature.
  • Forgetting site altitude in the air density.

Assumptions and limits

  • Dry air (humidity neglected on the air side): the air flows are dry-air values; on hot humid days the real volume flow is slightly larger.
  • Condensate leaves saturated (no subcooling); no air in-leakage on the steam side; fan heat is not added to the duty.
  • The ITD is reported for comparison only; the condenser pressure is an input, not checked against the ITD the bundles can achieve.
  • Dry air enthalpy by Shomate; below 25 °C the CO₂ and Ar terms are extrapolated slightly, a negligible effect for trace species.

References

  • IAPWS R7-97(2012) IF97
  • NIST Chemistry WebBook Shomate equations (air)

Questions and answers

How much air does an air-cooled condenser need?

Heat load divided by the air's enthalpy rise. 20 t/h of 92 % dry steam at 0.2 bar(a) gives 12.0 MW; air heated from 35 to 52 °C must flow at 705 kg/s, about 615 m³/s at ambient.

What is ITD?

The initial temperature difference: condensing temperature minus ambient air temperature, 25 K here. ACCs are sized on ITD; a hot day lowers it and raises the turbine back pressure.

Why do ACC plants run at higher back pressure?

Air is a poorer coolant than water and the dry bulb is above the wet bulb, so condensing temperatures of 50–65 °C are common, against 40–48 °C with wet cooling.

Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.