Fieldbus Segment Current and Voltage at the Last Device

Total current of a fieldbus segment and the voltage at the farthest device from the power conditioner voltage, trunk and spur cable resistance and device currents.

Thermal power plantProcess steam and utilities

Inputs

Examples: Illustrative 12 devices, 600 m trunkFull 16 devices, 1200 m trunkIntrinsically safe 13.5 V, 8 devices

Accepted: 9 to 32 V
Accepted: 1 to 32
Accepted: 1 to 50 mA
Accepted: 1 to 2,000 m
Accepted: 0 to 200 m
Accepted: 1 to 200 Ω/km
Accepted: 6 to 15 V

Results

Worst case with all devices lumped at the far end of the trunk: V = V_s − I_t·r·L_t − I_d·r·L_s (r is loop resistance, both conductors). Check the conditioner current limit and add spur short-circuit protection current where couplers are used.

Segment current144.00mA
Trunk voltage drop1.9008V
Voltage at the farthest device11.575V
Voltage margin2.5754V
Longest trunk for the minimum voltage706.48m

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 12 devices, 600 m trunk. The inputs, in the units selected above:

InputValue
Power conditioner output voltage24.000 V
Devices on the segment12.000 -
Current per device20.000 mA
Trunk length600.00 m
Longest spur length60.000 m
Cable loop resistance per km44.000 Ω/km
Minimum device voltage9.0000 V

Applying the formula below gives:

ResultValue
Segment current240.00 mA
Trunk voltage drop6.3360 V
Voltage at the farthest device17.611 V
Voltage margin8.6112 V
Longest trunk for the minimum voltage1,415.5 m

Open this example in the calculator and change any input.

Formula

\(I_t = nI_d, \quad V_{dev} = V_s - I_trL_t - I_drL_s\)

Variables

Symbol Meaning SI unit
\(V_s\) Power conditioner output voltage V
\(n\) Devices on the segment -
\(I_d\) Current per device A
\(L_t\) Trunk length m
\(L_s\) Longest spur length m
\(r\) Cable loop resistance per km Ω/m
\(V_{min}\) Minimum device voltage V
\(I_t\) Segment current A
\(\Delta V_t\) Trunk voltage drop V
\(V_{dev}\) Voltage at the farthest device V
\(V_{dev} - V_{min}\) Voltage margin V
\(L_{t,max}\) Longest trunk for the minimum voltage m

Method and standards

Segment budget.

Where it is used

  • Fieldbus network design.
  • Adding devices to existing segments.

Common mistakes

  • Using single-conductor instead of loop resistance.
  • Ignoring coupler current.

Assumptions and limits

  • DC voltage budget only.

References

  • Segment DC voltage budget
  • Liptak
  • Instrument Engineers' Handbook
  • Vol. 1 and 2 (CRC Press)

Questions and answers

Why lump the devices at the far end?

It is the worst case and gives a simple, conservative check; a detailed tool can place each device on its spur.

What limits segment length?

Voltage drop for bus-powered devices and signal attenuation; long trunks need fewer devices or a higher conditioner voltage.

What do the defaults represent?

An illustrative 24 V segment with 12 devices drawing 20 mA each, 600 m trunk and 60 m longest spur on cable of 44 Ω/km loop.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.