Worked example
Example: Illustrative DP transmitter 25 of 62 kPa. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Upper range limit | 62.000 kPa |
| Calibrated span | 25.000 kPa |
| Reference accuracy (% of span) | 0.065000 % |
| Temperature effect, URL part per 28 K | 0.025000 % |
| Temperature effect, span part per 28 K | 0.12500 % |
| Ambient change from calibration | 28.000 K |
| Static pressure zero effect per 69 bar (% URL) | 0.10000 % |
| Line static pressure | 69.000 bar |
Applying the formula below gives:
| Result | Value |
|---|---|
| Temperature effect (% span) | 0.18700 % |
| Static pressure effect (% span) | 0.24800 % |
| Total probable error (% span) | 0.31733 % |
| Total probable error | 0.079332 kPa |
| Worst case (arithmetic sum, % span) | 0.50000 % |
Open this example in the calculator and change any input.
Formula
\(e_T = \left(a_T\frac{URL}{S} + b_T\right)\frac{\Delta T}{28}, \quad e_{SP} = z_p\frac{URL}{S}\frac{p_{st}}{69\ \text{bar}}, \quad TPE = \sqrt{e_{ref}^2 + e_T^2 + e_{SP}^2}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(URL\) | Upper range limit | Pa |
| \(S\) | Calibrated span | Pa |
| \(e_{ref}\) | Reference accuracy (% of span) | - |
| \(a_T\) | Temperature effect, URL part per 28 K | - |
| \(b_T\) | Temperature effect, span part per 28 K | - |
| \(\Delta T\) | Ambient change from calibration | K |
| \(z_p\) | Static pressure zero effect per 69 bar (% URL) | - |
| \(p_{st}\) | Line static pressure | Pa |
| \(e_T\) | Temperature effect (% span) | - |
| \(e_{SP}\) | Static pressure effect (% span) | - |
| \(TPE\) | Total probable error (% span) | - |
| \(e_{max}\) | Worst case (arithmetic sum, % span) | - |
Method and standards
Total probable error.
Where it is used
- Transmitter selection and range choice.
- Flow and level measurement uncertainty.
Common mistakes
- Ignoring the URL-based terms at high turndown.
- Adding all terms arithmetically as the 'accuracy'.
Assumptions and limits
- Independent errors; specifications quoted as described.
References
- Root-sum-square combination of specification errors
Questions and answers
Why root sum square rather than adding?
The individual errors are independent and unlikely to peak together; RSS gives the probable total, the sum gives the worst case.
Why does turndown hurt accuracy?
Effects quoted in % of URL become a bigger share of a small span.
What do the defaults represent?
An illustrative 62 kPa URL DP transmitter calibrated to 25 kPa, ±0.065 % reference accuracy, 28 K ambient change, at 69 bar static pressure.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Lipták, Instrument Engineers' Handbook, Vol. 1: Process Measurement and Analysis, 4th ed. (CRC Press, 2003)