Worked example
Example: Illustrative 12 devices, 600 m trunk. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Power conditioner output voltage | 24.000 V |
| Devices on the segment | 12.000 - |
| Current per device | 20.000 mA |
| Trunk length | 600.00 m |
| Longest spur length | 60.000 m |
| Cable loop resistance per km | 44.000 Ω/km |
| Minimum device voltage | 9.0000 V |
Applying the formula below gives:
| Result | Value |
|---|---|
| Segment current | 240.00 mA |
| Trunk voltage drop | 6.3360 V |
| Voltage at the farthest device | 17.611 V |
| Voltage margin | 8.6112 V |
| Longest trunk for the minimum voltage | 1,415.5 m |
Open this example in the calculator and change any input.
Formula
\(I_t = nI_d, \quad V_{dev} = V_s - I_trL_t - I_drL_s\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(V_s\) | Power conditioner output voltage | V |
| \(n\) | Devices on the segment | - |
| \(I_d\) | Current per device | A |
| \(L_t\) | Trunk length | m |
| \(L_s\) | Longest spur length | m |
| \(r\) | Cable loop resistance per km | Ω/m |
| \(V_{min}\) | Minimum device voltage | V |
| \(I_t\) | Segment current | A |
| \(\Delta V_t\) | Trunk voltage drop | V |
| \(V_{dev}\) | Voltage at the farthest device | V |
| \(V_{dev} - V_{min}\) | Voltage margin | V |
| \(L_{t,max}\) | Longest trunk for the minimum voltage | m |
Method and standards
Segment budget.
Where it is used
- Fieldbus network design.
- Adding devices to existing segments.
Common mistakes
- Using single-conductor instead of loop resistance.
- Ignoring coupler current.
Assumptions and limits
- DC voltage budget only.
References
- Segment DC voltage budget
- Liptak
- Instrument Engineers' Handbook
- Vol. 1 and 2 (CRC Press)
Questions and answers
Why lump the devices at the far end?
It is the worst case and gives a simple, conservative check; a detailed tool can place each device on its spur.
What limits segment length?
Voltage drop for bus-powered devices and signal attenuation; long trunks need fewer devices or a higher conditioner voltage.
What do the defaults represent?
An illustrative 24 V segment with 12 devices drawing 20 mA each, 600 m trunk and 60 m longest spur on cable of 44 Ω/km loop.