Worked example
Example: Illustrative IIC barrier. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Barrier maximum external capacitance | 0.083000 µF |
| Barrier maximum external inductance | 3.0000 mH |
| Device internal capacitance | 0.005000 µF |
| Device internal inductance | 0.010000 mH |
| Cable capacitance per km | 100.00 nF/km |
| Cable inductance per km | 0.70000 mH/km |
Applying the formula below gives:
| Result | Value |
|---|---|
| Length limit by capacitance | 0.78000 km |
| Length limit by inductance | 4.2714 km |
| Maximum cable length | 0.78000 km |
Open this example in the calculator and change any input.
Formula
\(\ell_{max} = \min\left(\frac{C_o - C_i}{C_c}, \frac{L_o - L_i}{L_c}\right)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(C_o\) | Barrier maximum external capacitance | F |
| \(L_o\) | Barrier maximum external inductance | H |
| \(C_i\) | Device internal capacitance | F |
| \(L_i\) | Device internal inductance | H |
| \(C_c\) | Cable capacitance per km | F/m |
| \(L_c\) | Cable inductance per km | H/m |
| \(\ell_C\) | Length limit by capacitance | m |
| \(\ell_L\) | Length limit by inductance | m |
| \(\ell_{max}\) | Maximum cable length | m |
Method and standards
IS cable length.
Where it is used
- Hazardous-area loop design and inspection.
- Checking replacement cables.
Common mistakes
- Forgetting the device's internal values.
- Using the cable's loop rather than per-conductor values inconsistently.
Assumptions and limits
- Simple entity check; one barrier and one device.
References
- Entity concept for intrinsically safe loops
- Intrinsic safety entity concept: cable parameters against source Co and Lo
Questions and answers
Why does cable length matter for intrinsic safety?
Cable capacitance and inductance store energy that could be released as a spark; long cables store more.
Which limit usually governs?
Capacitance for high-voltage barriers (Group IIC especially), inductance for high-current circuits.
What do the defaults represent?
An illustrative barrier allowing 83 nF and 3 mH, a device with 5 nF and 10 µH, and cable of 100 nF/km and 0.7 mH/km.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.