Worked example
Example: Illustrative 25.6 kHz, 4096 samples, Hann. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Sampling rate | 25.600 kHz |
| Block size (samples) | 4,096.0 - |
| Window | Hann (1.50) |
Applying the formula below gives:
| Result | Value |
|---|---|
| Frequency resolution (bin width) | 6.2500 Hz |
| Record length | 160.00 ms |
| Nyquist frequency | 12,800 Hz |
| Usable lines (N/2.56) | 1,600.0 |
| Equivalent noise bandwidth | 9.3750 Hz |
Open this example in the calculator and change any input.
Formula
\(\Delta f = \frac{f_s}{N}, \quad T = \frac{N}{f_s}, \quad f_N = \frac{f_s}2, \quad ENBW = k_w\,\Delta f\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(f_s\) | Sampling rate | 1/s |
| \(N\) | Block size (samples) | - |
| \(\text{window}\) | Window | - |
| \(\Delta f\) | Frequency resolution (bin width) | 1/s |
| \(T\) | Record length | s |
| \(f_N\) | Nyquist frequency | 1/s |
| \(n_L\) | Usable lines (N/2.56) | - |
| \(ENBW\) | Equivalent noise bandwidth | 1/s |
Method and standards
FFT resolution.
Where it is used
- Setting up vibration and acoustic analysers.
- Separating close frequencies such as motor slip sidebands.
Common mistakes
- Expecting resolution from a higher sampling rate alone.
- Using the bin width instead of ENBW for noise levels.
Assumptions and limits
- Single block; no zero padding.
References
- Discrete Fourier transform resolution and window noise bandwidth
Questions and answers
How do I get 1 Hz resolution?
Use a record of 1 s: for example 25.6 kHz sampling and 25,600 samples, or 2.56 kHz and 2,560.
Why 2.56?
Analysers sample at 2.56 times the maximum frequency so the anti-aliasing filter can roll off before the Nyquist frequency.
What do the defaults represent?
An illustrative vibration analyser sampling at 25.6 kHz with 4,096-sample blocks and a Hann window.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Oppenheim and Schafer, Discrete-Time Signal Processing, 3rd ed. (Pearson, 2010), Harris, On the use of windows for harmonic analysis with the discrete Fourier transform, Proc. IEEE 66 (1978)