Worked example
Example: Orifice set for 10.5 bar(a) sat, running at 8 bar(a) sat, reads 10 t/h. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Meter reading (mass flow) | 10,000 kg/h |
| Meter type | Differential pressure (orifice, nozzle, venturi) |
| Design pressure (absolute) | 10.500 bar |
| Design steam condition | Dry saturated |
| Design temperature (superheated only) | 250.00 °C |
| Actual pressure (absolute) | 8.0000 bar |
| Actual steam condition | Dry saturated |
| Actual temperature (superheated only) | 250.00 °C |
Applying the formula below gives:
| Result | Value |
|---|---|
| Corrected (true) steam flow | 8,785.7 kg/h |
| Correction factor | 0.87857 |
| Steam density at design | 5.3907 kg/m³ |
| Steam density actual | 4.1610 kg/m³ |
Open this example in the calculator and change any input.
Formula
\(k_{DP} = \sqrt{\frac{\rho_a}{\rho_d}} \qquad k_{vol} = \frac{\rho_a}{\rho_d} \qquad \dot m = k\,\dot m_i\)
Variables
| Symbol | Meter or quantity | SI unit |
|---|---|---|
| \(\dot m_i\) | meter reading | kg/s |
| \(\text{meter}\) | differential pressure or volumetric | – |
| \(p_d\) | design pressure, absolute | Pa |
| \(\text{state}_d\) | design steam condition | – |
| \(T_d\) | design temperature | K |
| \(p_a\) | actual pressure, absolute | Pa |
| \(\text{state}_a\) | actual steam condition | – |
| \(T_a\) | actual temperature | K |
| \(\dot m\) | corrected steam flow | kg/s |
| \(k\) | correction factor | – |
| \(\rho_d\) | steam density at design | kg/m³ |
| \(\rho_a\) | steam density actual | kg/m³ |
Method and standards
Differential-pressure meters follow √(Δp·ρ) (the principle of ISO 5167); volumetric meters measure volume, so mass scales with density. Steam densities from FireCAD's IAPWS-IF97.
Where it is used
- Correcting steam totals for efficiency and cost reports.
- Checking whether a meter needs compensation.
- Reconciling boiler and user steam meters.
Common mistakes
- Using gauge pressure.
- Assuming saturated steam when it is superheated.
- Correcting a meter that already has live compensation.
Assumptions and limits
- Dry steam; the meter's other coefficients unchanged.
- Wet steam cannot be entered. A DP meter in wet steam reads high (the liquid adds to the differential), so applying only this density correction under-corrects; wet steam needs a two-phase meter correction and a known dryness fraction.
References
- IAPWS R7-97(2012) IF97
- ISO 5167 (DP meters: mass flow proportional to the square root of density)
Questions and answers
How wrong is an uncompensated steam meter?
An orifice meter set up for 10.5 bar(a) saturated steam but running at 8 bar(a) reads 10 t/h when only 8.79 t/h flows, 14 % high. A vortex meter showing mass with fixed density errs twice as much, because it measures volume.
Why the square root for orifice meters?
The differential pressure is ρv²/2, so mass flow is proportional to √(Δp·ρ); with ρ fixed in the transmitter, the reading scales with √(ρ_actual/ρ_design).
How do I avoid this?
Fit pressure (and for superheated steam, temperature) compensation in the flow computer, or correct the totals with this factor.