Worked example
Example: Suction line 35 mm. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Refrigerant mass flow | 900.00 kg/h |
| Refrigerant density in the line | 20.000 kg/m³ |
| Inside diameter | 35.000 mm |
| Target velocity | 10.000 m/s |
Applying the formula below gives:
| Result | Value |
|---|---|
| Velocity | 12.992 m/s |
| Volume flow | 45.000 m³/h |
| Bore for the target velocity | 39.894 mm |
Open this example in the calculator and change any input.
Formula
\(v = \frac{\dot m}{\rho\, \pi D^2/4}, \quad D_t = \sqrt{\frac{4\dot m}{\pi\rho v_t}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot m\) | Refrigerant mass flow | kg/s |
| \(\rho\) | Refrigerant density in the line | kg/m³ |
| \(D\) | Inside diameter | m |
| \(v_t\) | Target velocity | m/s |
| \(v\) | Velocity | m/s |
| \(\dot V\) | Volume flow | m³/s |
| \(D_t\) | Bore for the target velocity | m |
Method and standards
Continuity.
Where it is used
- Refrigeration plant piping.
- Checking site-run lines.
Common mistakes
- Liquid density for suction lines.
- Outside instead of inside diameter.
Assumptions and limits
- Single phase in the line.
References
- Continuity v = ṁ/(ρA)
Questions and answers
0.25 kg/s of suction gas at 20 kg/m³ in a 35 mm bore?
About 13 m/s.
Why does velocity matter?
Too low and oil stays in the lines; too high and pressure drop and noise rise.
Liquid lines?
Much lower velocities, typically below 1.5 m/s.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.