FireCADCalc

Refrigerant Line Velocity and Size Check

Velocity of refrigerant in a suction, discharge or liquid line from mass flow, line bore and refrigerant density, with the bore for a target velocity.

Food, dairy and textileRefrigeration and air-conditioning mechanic examinations

Inputs

Examples: Suction line 35 mmLiquid line 16 mm

From the refrigerant's property tables at the line conditions.
Your design guide's range for the line and refrigerant (suction lines must still return oil).

Results

Velocity1.0812m/s
Volume flow0.78261m³/h
Bore for the target velocity16.637mm

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Suction line 35 mm. The inputs, in the units selected above:

InputValue
Refrigerant mass flow900.00 kg/h
Refrigerant density in the line20.000 kg/m³
Inside diameter35.000 mm
Target velocity10.000 m/s

Applying the formula below gives:

ResultValue
Velocity12.992 m/s
Volume flow45.000 m³/h
Bore for the target velocity39.894 mm

Open this example in the calculator and change any input.

Formula

\(v = \frac{\dot m}{\rho\, \pi D^2/4}, \quad D_t = \sqrt{\frac{4\dot m}{\pi\rho v_t}}\)

Variables

Symbol Meaning SI unit
\(\dot m\) Refrigerant mass flow kg/s
\(\rho\) Refrigerant density in the line kg/m³
\(D\) Inside diameter m
\(v_t\) Target velocity m/s
\(v\) Velocity m/s
\(\dot V\) Volume flow m³/s
\(D_t\) Bore for the target velocity m

Method and standards

Continuity.

Where it is used

  • Refrigeration plant piping.
  • Checking site-run lines.

Common mistakes

  • Liquid density for suction lines.
  • Outside instead of inside diameter.

Assumptions and limits

  • Single phase in the line.

References

  • Continuity v = ṁ/(ρA)

Questions and answers

0.25 kg/s of suction gas at 20 kg/m³ in a 35 mm bore?

About 13 m/s.

Why does velocity matter?

Too low and oil stays in the lines; too high and pressure drop and noise rise.

Liquid lines?

Much lower velocities, typically below 1.5 m/s.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators