Heat Pump Seasonal Performance by the Bin Method

Seasonal heat, electricity and SCOP of a heat pump from four outdoor temperature bins with hours and COP and a load line from the design point.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: 10 kW house, four binsColder climate, 8 kW, backup in bin 1

Results

Linear load line from zero at the balance temperature to the design load. The COP for each bin should include defrost and cycling losses; backup heater use below the bivalent point is not modelled (enter its COP as 1 for those bins).

Seasonal heat delivered16,077kWh
Seasonal electricity6,982.6kWh
Seasonal COP2.3025

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 10 kW house, four bins. The inputs, in the units selected above:

InputValue
Design heat load10.000 kW
Design outdoor temperature-5.0000 °C
Balance (no-load) temperature15.000 °C
Bin 1 temperature-2.0000 °C
Bin 1 hours500.00 h
Bin 1 COP2.6000 -
Bin 2 temperature3.0000 °C
Bin 2 hours1,200.0 h
Bin 2 COP3.1000 -
Bin 3 temperature8.0000 °C
Bin 3 hours1,500.0 h
Bin 3 COP3.7000 -
Bin 4 temperature12.000 °C
Bin 4 hours1,000.0 h
Bin 4 COP4.3000 -

Applying the formula below gives:

ResultValue
Seasonal heat delivered18,200 kWh
Seasonal electricity5,725.0 kWh
Seasonal COP3.1791

Open this example in the calculator and change any input.

Formula

\(Q_i = Q_d\frac{t_b - t_i}{t_b - t_d}, \quad SCOP = \frac{\sum Q_ih_i}{\sum Q_ih_i/COP_i}\)

Variables

Symbol Meaning SI unit
\(Q_d\) Design heat load W
\(t_d\) Design outdoor temperature K
\(t_b\) Balance (no-load) temperature K
\(t_1\) Bin 1 temperature K
\(h_1\) Bin 1 hours s
\(COP_1\) Bin 1 COP -
\(t_2\) Bin 2 temperature K
\(h_2\) Bin 2 hours s
\(COP_2\) Bin 2 COP -
\(t_3\) Bin 3 temperature K
\(h_3\) Bin 3 hours s
\(COP_3\) Bin 3 COP -
\(t_4\) Bin 4 temperature K
\(h_4\) Bin 4 hours s
\(COP_4\) Bin 4 COP -
\(E_h\) Seasonal heat delivered J
\(E_e\) Seasonal electricity J
\(SCOP\) Seasonal COP -

Method and standards

Bin method.

Where it is used

  • Heat pump selection and running cost.
  • Comparing heat pump models.

Common mistakes

  • Using rated COP for every hour.
  • Ignoring defrost.

Assumptions and limits

  • Linear load line; four bins.
  • The heat pump is assumed to meet the whole load in every bin; its capacity limit is not modelled. Below the bivalent point, where a backup heater carries part of the load, enter a lower blended COP (1 for an all-electric backup bin).

References

  • Bin method (ASHRAE Handbook—Fundamentals (2017), ch. 19, energy estimating)

Questions and answers

Why bins rather than one COP?

COP and load both change with outdoor temperature; most heating hours are at mild temperatures where COP is high.

Where do the bin hours come from?

Local weather data: hours per year in each outdoor temperature band during the heating season.

What do the defaults represent?

A 10 kW (design) house load with four outdoor temperature bins and COPs from a maker's data sheet.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.