Worked example
Example: 10 kW house, four bins. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Design heat load | 10.000 kW |
| Design outdoor temperature | -5.0000 °C |
| Balance (no-load) temperature | 15.000 °C |
| Bin 1 temperature | -2.0000 °C |
| Bin 1 hours | 500.00 h |
| Bin 1 COP | 2.6000 - |
| Bin 2 temperature | 3.0000 °C |
| Bin 2 hours | 1,200.0 h |
| Bin 2 COP | 3.1000 - |
| Bin 3 temperature | 8.0000 °C |
| Bin 3 hours | 1,500.0 h |
| Bin 3 COP | 3.7000 - |
| Bin 4 temperature | 12.000 °C |
| Bin 4 hours | 1,000.0 h |
| Bin 4 COP | 4.3000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Seasonal heat delivered | 18,200 kWh |
| Seasonal electricity | 5,725.0 kWh |
| Seasonal COP | 3.1791 |
Open this example in the calculator and change any input.
Formula
\(Q_i = Q_d\frac{t_b - t_i}{t_b - t_d}, \quad SCOP = \frac{\sum Q_ih_i}{\sum Q_ih_i/COP_i}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q_d\) | Design heat load | W |
| \(t_d\) | Design outdoor temperature | K |
| \(t_b\) | Balance (no-load) temperature | K |
| \(t_1\) | Bin 1 temperature | K |
| \(h_1\) | Bin 1 hours | s |
| \(COP_1\) | Bin 1 COP | - |
| \(t_2\) | Bin 2 temperature | K |
| \(h_2\) | Bin 2 hours | s |
| \(COP_2\) | Bin 2 COP | - |
| \(t_3\) | Bin 3 temperature | K |
| \(h_3\) | Bin 3 hours | s |
| \(COP_3\) | Bin 3 COP | - |
| \(t_4\) | Bin 4 temperature | K |
| \(h_4\) | Bin 4 hours | s |
| \(COP_4\) | Bin 4 COP | - |
| \(E_h\) | Seasonal heat delivered | J |
| \(E_e\) | Seasonal electricity | J |
| \(SCOP\) | Seasonal COP | - |
Method and standards
Bin method.
Where it is used
- Heat pump selection and running cost.
- Comparing heat pump models.
Common mistakes
- Using rated COP for every hour.
- Ignoring defrost.
Assumptions and limits
- Linear load line; four bins.
- The heat pump is assumed to meet the whole load in every bin; its capacity limit is not modelled. Below the bivalent point, where a backup heater carries part of the load, enter a lower blended COP (1 for an all-electric backup bin).
References
- Bin method (ASHRAE Handbook—Fundamentals (2017), ch. 19, energy estimating)
Questions and answers
Why bins rather than one COP?
COP and load both change with outdoor temperature; most heating hours are at mild temperatures where COP is high.
Where do the bin hours come from?
Local weather data: hours per year in each outdoor temperature band during the heating season.
What do the defaults represent?
A 10 kW (design) house load with four outdoor temperature bins and COPs from a maker's data sheet.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.