Worked example
Example: 10 m³/s, 1,000 Pa, 250 Pa set point, 60 % flow. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Design air flow | 36,000 m³/h |
| Design fan pressure | 1,000.0 Pa |
| Static pressure set point (fixed part) | 250.00 Pa |
| Overall fan efficiency | 65.000 % |
| Flow fraction | 60.000 % |
| Hours at this flow per year | 4,000.0 h |
Applying the formula below gives:
| Result | Value |
|---|---|
| Fan pressure at part flow | 520.00 Pa |
| Fan power at part flow | 4.8000 kW |
| Fan power at design | 15.385 kW |
| Power ratio | 31.200 % |
| Cube-law ratio | 21.600 % |
| Energy saved against constant volume | 42,338 kWh |
Open this example in the calculator and change any input.
Formula
\(\Delta p = \Delta p_{sp} + (\Delta p_d - \Delta p_{sp})r^2, \quad W = \frac{r\dot V_d\Delta p}{\eta}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot V_d\) | Design air flow | m³/s |
| \(\Delta p_d\) | Design fan pressure | Pa |
| \(\Delta p_{sp}\) | Static pressure set point (fixed part) | Pa |
| \(\eta\) | Overall fan efficiency | - |
| \(r\) | Flow fraction | - |
| \(t\) | Hours at this flow per year | s |
| \(\Delta p\) | Fan pressure at part flow | Pa |
| \(W\) | Fan power at part flow | W |
| \(W_d\) | Fan power at design | W |
| \(W/W_d\) | Power ratio | - |
| \(r^3\) | Cube-law ratio | - |
| \(\Delta E\) | Energy saved against constant volume | J |
Method and standards
Fan and system curves.
Where it is used
- VAV retrofit savings.
- Comparing control strategies.
Common mistakes
- Assuming the cube law with a fixed set point.
- Ignoring drive losses at low speed.
Assumptions and limits
Fan efficiency is held at its design value at part flow. In practice fan, motor and drive efficiencies fall at low load, so the part-flow power is higher and the saving smaller than shown.
Constant efficiency; quadratic system curve above the set point.
References
- ASHRAE Handbook—Fundamentals (2017)
- ch. 21 and ASHRAE Handbook—HVAC Applications (2019)
- ch. 42 (fan–system interaction with a fixed static set point)
Questions and answers
Why not the full cube-law saving?
The duct static set point keeps part of the pressure constant, so power falls more slowly than flow cubed.
What is static pressure reset?
Lowering the set point until the most open VAV box is nearly fully open; it recovers much of the lost saving.
What do the defaults represent?
A 10 m³/s air handler at 1,000 Pa with a 250 Pa set point running at 60 % flow.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.