Rectangular Duct Equivalent Diameter

Equivalent round diameter (Huebscher) and hydraulic diameter of a rectangular duct, with area, aspect ratio and velocities for a flow.

Thermic fluid heatingFan and blower

Inputs

Examples: Duct 600 x 400 mm, 2 m³/sSquare duct 500 x 500 mmFlue duct 2 000 x 1 200 mm, 30 m³/s

Results

Equivalent diameter (same friction at the same flow)546.58mm
Hydraulic diameter500.00mm
Duct area0.25000m²
Aspect ratio1.0000

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Duct 600 x 400 mm, 2 m³/s. The inputs, in the units selected above:

InputValue
Duct width600.00 mm
Duct height400.00 mm
Volume flow (0 = skip)7,200.0 m³/h

Applying the formula below gives:

ResultValue
Equivalent diameter (same friction at the same flow)532.81 mm
Hydraulic diameter480.00 mm
Duct area0.24000 m²
Aspect ratio1.5000
Velocity in the rectangular duct8.3333 m/s
Velocity in the equivalent round duct8.9699 m/s

Open this example in the calculator and change any input.

Formula

\(D_e = \frac{1.30\,(a\,b)^{0.625}}{(a+b)^{0.25}} \qquad D_h = \frac{2\,a\,b}{a+b} \qquad A = a\,b \qquad AR = \frac{\max(a,b)}{\min(a,b)}\)

\(v = \frac{\dot V}{A} \qquad v_e = \frac{4\,\dot V}{\pi D_e^2}\)

Variables

Symbol Meaning SI unit
\(a\) duct width m
\(b\) duct height m
\(\dot V\) volume flow m³/s
\(D_e\) equivalent diameter (same friction at the same flow) m
\(D_h\) hydraulic diameter m
\(A\) duct area m²
\(AR\) aspect ratio –
\(v\) velocity in the rectangular duct m/s
\(v_e\) velocity in the equivalent round duct m/s

Method and standards

R.G. Huebscher's equation (ASHVE Transactions, 1948), as given in the Duct Design chapter of the ASHRAE Handbook—Fundamentals, and the hydraulic diameter 4A/P.

Where it is used

  • Duct pressure drop with round-duct friction charts.
  • Converting duct sizes during layout.
  • Fan and draught calculations.

Common mistakes

  • Using hydraulic diameter where equal-friction equivalent diameter is meant, or the reverse.
  • Very flat ducts outside the correlation range.
  • Forgetting the actual velocity in the rectangular duct.

Assumptions and limits

  • Huebscher's tests covered aspect ratios up to 8:1; beyond that the result is approximate.
  • Same roughness and fluid in both ducts; turbulent flow.
  • For pressure drop use D_e with the volume flow, or D_h with the true velocity; do not mix the two.

References

  • Huebscher (1948)
  • ASHRAE Handbook—Fundamentals (Duct Design)

Questions and answers

What is the equivalent diameter of a rectangular duct?

The round duct with the same friction loss per metre at the same volume flow: De = 1.30·(a·b)^0.625/(a+b)^0.25. A 600 × 400 mm duct is equivalent to a 533 mm round duct.

How is it different from the hydraulic diameter?

The hydraulic diameter 2ab/(a+b) gives the same friction at the same velocity; use it with the actual duct velocity. The Huebscher diameter gives the same friction at the same flow; use it with the flow in a round-duct friction chart or calculator.

Why is the velocity different in the equivalent duct?

The equivalent round duct has a smaller area than the rectangle, so the same flow moves faster in it. The friction per metre is nevertheless the same.

Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.