Air Outlet Throw and Terminal Velocity (Free Jet)

Outlet velocity, centreline velocity at a distance, and throw to 0.75, 0.5 and 0.25 m/s for a grille or diffuser from flow, effective area and its throw constant.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: Sidewall grille 0.15 m³/s, 0.02 m², K 5Ceiling diffuser 0.3 m³/s, 0.05 m², K 1.4

Results

Fully developed region of an isothermal free jet: v_x = Kv₀√A₀/x. K is about 5–6 for compact jets from grilles and nozzles and 1–2 for radial ceiling diffusers (makers' data). Surface (Coanda) attachment lengthens throw by about 40 %; buoyancy changes it for heated or cooled air.

Outlet velocity7.5000m/s
Centreline velocity at x1.7678m/s
Throw to 0.75 m/s7.0711m
Throw to 0.50 m/s10.607m
Throw to 0.25 m/s21.213m

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Sidewall grille 0.15 m³/s, 0.02 m², K 5. The inputs, in the units selected above:

InputValue
Air flow through the outlet540.00 m³/h
Effective (core × free area) outlet area0.020000 m²
Throw constant of the outlet5.0000 -
Distance from the outlet3.0000 m

Applying the formula below gives:

ResultValue
Outlet velocity7.5000 m/s
Centreline velocity at x1.7678 m/s
Throw to 0.75 m/s7.0711 m
Throw to 0.50 m/s10.607 m
Throw to 0.25 m/s21.213 m

Open this example in the calculator and change any input.

Formula

\(v_x = \min\left(v_0,\ \frac{Kv_0\sqrt{A_0}}{x}\right), \quad T_{v_t} = \frac{Kv_0\sqrt{A_0}}{v_t}\)

Variables

Symbol Meaning SI unit
\(\dot V\) Air flow through the outlet m³/s
\(A_0\) Effective (core × free area) outlet area m²
\(K\) Throw constant of the outlet -
\(x\) Distance from the outlet m
\(v_0\) Outlet velocity m/s
\(v_x\) Centreline velocity at x m/s
\(T_{0.75}\) Throw to 0.75 m/s m
\(T_{0.50}\) Throw to 0.50 m/s m
\(T_{0.25}\) Throw to 0.25 m/s m

Method and standards

Free-jet decay.

Where it is used

  • Supply grille and nozzle selection.
  • Checking draughts in occupied zones.

Common mistakes

  • Using face area instead of effective area.
  • Ignoring Coanda effect near ceilings.

Assumptions and limits

  • Isothermal jet; fully developed region. Distances within about K√A₀ of the outlet are flagged, and v_x is capped at v₀ there.
  • Terminal velocities are 0.75, 0.5 and 0.25 m/s in every unit system; US data at 150, 100 and 50 fpm (0.762, 0.508, 0.254 m/s) give throws about 1.6 % shorter.

References

  • ASHRAE Handbook—Fundamentals (2017)
  • ch. 20 (Room air distribution: free-jet centreline velocity v_x/v₀ = K√A₀/x)

Questions and answers

What throw should I choose?

Throw to 0.25 m/s (T₅₀ or T₂₅ depending on convention) should reach about three-quarters of the distance to the opposite wall without striking occupants at high speed.

Why is the effective area smaller than the face?

Grilles have blades and frames; only the free area passes air, and the vena contracta shrinks it further.

What do the defaults represent?

A sidewall grille passing a modest flow through a small effective area with a compact-jet throw constant.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.