FireCADCalc

Fuel Oil Viscosity Converter: cSt, Redwood No. 1 and Saybolt

Convert fuel oil viscosity between centistokes, Redwood No. 1 seconds and Saybolt Universal seconds (SUS), in either direction.

Thermal power plantProcess steam and utilities

Inputs

Examples: 180 cSt at 100 F1000 Redwood No. 1 seconds60 Redwood seconds500 SUS at 210 F

Accepted: 1 to 100,000
Saybolt seconds depend slightly on the test temperature at the same cSt; 37.8 °C (100 °F) is the reference.Accepted: -20 to 150 °C

Results

Redwood No. 1 seconds use ν = 0.26 t − 171.5/t below 100 s and ν = 0.247 t − 50/t above (ν in cSt). Saybolt Universal seconds use the ASTM D2161 equation at 100 °F with its temperature correction 1 + 0.000061 (t − 100 °F). Above about 100 cSt Redwood seconds are about 4.05 × cSt and Saybolt seconds about 4.63 × cSt. Viscosity grades of fuel oil are stated at a temperature (50 °C for furnace oil in cSt, 100 °F for Redwood in older specifications): converting the unit does not convert the temperature.

Kinematic viscosity246.95cSt
Redwood No. 1 seconds1,000.0
Saybolt Universal seconds1,144.0

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 180 cSt at 100 F. The inputs, in the units selected above:

InputValue
Value entered isKinematic viscosity, cSt
Value180.00 -
Test temperature (for the Saybolt temperature correction)37.778 °C

Applying the formula below gives:

ResultValue
Kinematic viscosity180.00 cSt
Redwood No. 1 seconds729.02
Saybolt Universal seconds833.90

Open this example in the calculator and change any input.

Formula

\(\nu = 0.26\,t - \frac{171.5}{t}\ (t<100\ \text{s}), \quad \nu = 0.247\,t - \frac{50}{t}\ (t \ge 100\ \text{s})\)

\(t_{SU} = \left[4.6324\nu + \frac{1 + 0.03264\nu}{(3930.2 + 262.7\nu + 23.97\nu^2 + 1.646\nu^3)\,10^{-5}}\right]\left[1 + 0.000061\,(t_F - 100)\right]\)

Variables

Symbol Meaning SI unit
\(\text{from}\) Value entered is -
\(x\) Value -
\(t\) Test temperature (for the Saybolt temperature correction) K
\(\nu\) Kinematic viscosity m²/s
\(t_{R1}\) Redwood No. 1 seconds -
\(t_{SU}\) Saybolt Universal seconds -

Method and standards

Viscosity conversion.

Where it is used

  • Reading older fuel oil specifications in Redwood seconds.
  • Converting American SUS data to cSt.

Common mistakes

  • Converting the unit but not the temperature of the viscosity grade.
  • Using Redwood No. 1 equations for Redwood No. 2 (admiralty) seconds, which are about a tenth.

Assumptions and limits

  • Newtonian oil; the conversions are empirical fits to the viscometer calibrations.

References

  • ASTM D2161 conversion of kinematic viscosity to Saybolt Universal viscosity (equation method)
  • Redwood No. 1 viscometer conversion equations (Institute of Petroleum, two ranges)

Questions and answers

How do I convert Redwood seconds to cSt?

ν = 0.247 t − 50/t above 100 s: 1,000 Redwood seconds is 247 cSt.

What is 180 cSt in Redwood seconds?

About 729 Redwood No. 1 seconds and 834 Saybolt Universal seconds.

What do the defaults represent?

A 180 cSt fuel oil at the 100 °F Saybolt reference temperature.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.