Worked example
Example: 100 TR, 5 K. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Cooling capacity (choose its unit) | 100.00 TR |
| Chilled-water temperature difference | 5.0000 K |
Applying the formula below gives:
| Result | Value |
|---|---|
| Capacity in tons of refrigeration | 100.00 TR |
| Capacity in kW | 351.69 kW |
| Capacity in Btu/h | 1,200,000 Btu/h |
| Capacity in kcal/h | 302,395 kcal/h |
| Chilled-water flow for the temperature difference | 60.600 m³/h |
Open this example in the calculator and change any input.
Formula
\(1\ \text{TR} = 12\,000\ \text{Btu/h} = 3.517\ \text{kW}, \quad \dot V = \frac{Q}{\rho c_p \Delta T}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q\) | Cooling capacity (choose its unit) | W |
| \(\Delta T\) | Chilled-water temperature difference | K |
| \(\dot V\) | Chilled-water flow for the temperature difference | m³/s |
Method and standards
Refrigeration units.
Where it is used
- Comparing chillers rated in TR and kW.
- First estimate of chilled-water flow.
Common mistakes
- Using the metric ton of refrigeration (3.86 kW, rarely used) instead of the standard TR.
- Confusing cooling capacity (TR) with compressor power (kW).
Assumptions and limits
- Water properties at about 20 °C for the flow.
References
- Unit definitions per NIST SP 811 and the SI Brochure (exact where defined)
- Chilled-water flow from Q = ρ c_p V ΔT
Questions and answers
How many kW is 1 TR?
3.517 kW (12,000 Btu/h).
What chilled-water flow does 1 TR need?
About 0.6 m³/h at a 5 K difference, or 2.4 US gpm at 10 °F.
What do the defaults represent?
A 100 TR chiller (352 kW) with a 5 K chilled-water difference.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.