Refrigeration Capacity Converter (TR, kW, Btu/h, kcal/h)

Convert chiller and air-conditioning capacity between tons of refrigeration, kW, Btu/h and kcal/h, with the chilled-water flow for a temperature drop.

Inputs

Examples: 100 TR, 5 K500 kW, 6 K

Accepted: 0 to 284,350 TR
Accepted: 0.1 to 30 K

Results

One ton of refrigeration is 12,000 Btu/h, the heat absorbed by melting one short ton of ice in a day: 3.517 kW or 3,024 kcal/h. The chilled-water flow is Q/(ρ c_p ΔT) with water at about 20 °C (998.2 kg/m³, 4.186 kJ/kg·K): about 0.6 m³/h per TR at 5 K.

Capacity in tons of refrigeration100.00TR
Capacity in kW351.69kW
Capacity in Btu/h1,200,000Btu/h
Capacity in kcal/h302,395kcal/h
Chilled-water flow for the temperature difference60.600m³/h

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 100 TR, 5 K. The inputs, in the units selected above:

InputValue
Cooling capacity (choose its unit)100.00 TR
Chilled-water temperature difference5.0000 K

Applying the formula below gives:

ResultValue
Capacity in tons of refrigeration100.00 TR
Capacity in kW351.69 kW
Capacity in Btu/h1,200,000 Btu/h
Capacity in kcal/h302,395 kcal/h
Chilled-water flow for the temperature difference60.600 m³/h

Open this example in the calculator and change any input.

Formula

\(1\ \text{TR} = 12\,000\ \text{Btu/h} = 3.517\ \text{kW}, \quad \dot V = \frac{Q}{\rho c_p \Delta T}\)

Variables

Symbol Meaning SI unit
\(Q\) Cooling capacity (choose its unit) W
\(\Delta T\) Chilled-water temperature difference K
\(\dot V\) Chilled-water flow for the temperature difference m³/s

Method and standards

Refrigeration units.

Where it is used

  • Comparing chillers rated in TR and kW.
  • First estimate of chilled-water flow.

Common mistakes

  • Using the metric ton of refrigeration (3.86 kW, rarely used) instead of the standard TR.
  • Confusing cooling capacity (TR) with compressor power (kW).

Assumptions and limits

  • Water properties at about 20 °C for the flow.

References

  • Unit definitions per NIST SP 811 and the SI Brochure (exact where defined)
  • Chilled-water flow from Q = ρ c_p V ΔT

Questions and answers

How many kW is 1 TR?

3.517 kW (12,000 Btu/h).

What chilled-water flow does 1 TR need?

About 0.6 m³/h at a 5 K difference, or 2.4 US gpm at 10 °F.

What do the defaults represent?

A 100 TR chiller (352 kW) with a 5 K chilled-water difference.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.