Worked example
Example: Same pool with a bubble cover 12 h. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Pool surface area | 72.000 m² |
| Pool temperature | 25.000 °C |
| Monthly mean air temperature | 16.000 °C |
| Monthly mean relative humidity | 70.000 % |
| Air pressure | 101.33 kPa |
| Wind speed at the pool (1/5–1/10 of the weather-station value) | 3.0000 m/s |
| Monthly average daily radiation on a horizontal surface | 19.100 MJ/m² |
| Monthly clearness index (weighting of sky temperature) | 53.000 % |
| Surface transmittance | 92.000 % |
| Pool absorptance (0.6 to 0.9) | 60.000 % |
| Days in the month | 30.000 - |
| Share of the time covered | 50.000 % |
| Cover type | Bubble cover (stops evaporation, cuts convection) |
Applying the formula below gives:
| Result | Value |
|---|---|
| Dew point | 10.538 °C |
| Mean sky temperature | 7.7381 °C |
| Solar energy absorbed | 22.773 GJ |
| Radiation loss | 17.748 GJ |
| Evaporation loss (uncovered) | 44.753 GJ |
| Convection loss (uncovered) | 19.855 GJ |
| Heating load, never covered | 59.583 GJ |
| Heating load with the cover | 27.279 GJ |
Open this example in the calculator and change any input.
Formula
\(q_e = P_a[35V + 43(T_p - T_a)^{1/3}](\omega_p - \omega_a), \quad q_c = q_e\,0.0006\frac{T_p - T_a}{\omega_p - \omega_a}\)
\(Q_r = A\sigma(T_p^4 - \bar T_{sky}^4)\Delta t, \quad Q_s = A\bar H\tau\alpha N\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(A\) | Pool surface area | m² |
| \(T_p\) | Pool temperature | K |
| \(\bar T_a\) | Monthly mean air temperature | K |
| \(\phi\) | Monthly mean relative humidity | - |
| \(P_a\) | Air pressure | Pa |
| \(V\) | Wind speed at the pool (1/5–1/10 of the weather-station value) | m/s |
| \(\bar H\) | Monthly average daily radiation on a horizontal surface | J/m² |
| \(\bar K_T\) | Monthly clearness index (weighting of sky temperature) | - |
| \(\tau\) | Surface transmittance | - |
| \(\alpha\) | Pool absorptance (0.6 to 0.9) | - |
| \(N\) | Days in the month | - |
| \(f_c\) | Share of the time covered | - |
| \(\text{cover}\) | Cover type | - |
| \(T_{dp}\) | Dew point | K |
| \(\bar T_{sky}\) | Mean sky temperature | K |
| \(Q_s\) | Solar energy absorbed | J |
| \(Q_r\) | Radiation loss | J |
| \(Q_e\) | Evaporation loss (uncovered) | J |
| \(Q_c\) | Convection loss (uncovered) | J |
| \(L_0\) | Heating load, never covered | J |
| \(L\) | Heating load with the cover | J |
Method and standards
Monthly energy balance of an outdoor pool.
Where it is used
- Sizing solar pool heaters and heat pumps.
- Estimating cover savings.
Common mistakes
- Using weather-station wind speed directly.
- Forgetting evaporation, the largest loss.
Assumptions and limits
- Monthly averages; empirical evaporation equation.
Questions and answers
Which loss is largest?
Evaporation, typically half or more of the total; that is why a cover saves so much.
Why use a reduced wind speed?
Pools are sheltered by fences and buildings; Wei et al. suggest one-fifth to one-tenth of the weather-station wind.
What do the defaults represent?
An illustrative case: Same pool with a bubble cover 12 h. Replace the inputs with your own data.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.