Worked example
Example: Illustrative: 1050 W/m2, selective single-glazed collector, 35 C ambient, fluid boils at 140 C. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Radiation on the collector | 1,050.0 W/m² |
| Transmittance–absorptance product | 80.000 % |
| Number of glass covers | 1.0000 - |
| Plate emittance (selective 0.1, black paint 0.95) | 12.000 % |
| Glass emittance | 88.000 % |
| Collector slope | 40.000 ° |
| Ambient temperature | 35.000 °C |
| Wind heat transfer coefficient | 8.0000 W/(m²·K) |
| Back insulation conductivity | 0.040000 W/(m·K) |
| Back insulation thickness | 50.000 mm |
| Edge loss coefficient | 0.30000 W/(m²·K) |
| Boiling point of the collector fluid at system pressure | 140.00 °C |
Applying the formula below gives:
| Result | Value |
|---|---|
| Stagnation plate temperature | 189.28 °C |
| Loss coefficient at that temperature | 5.4446 W/(m²·K) |
| Top loss coefficient | 4.3446 W/(m²·K) |
| Absorbed radiation | 840.00 W/m² |
| Margin to boiling (negative = boils) | -49.282 K |
Open this example in the calculator and change any input.
Formula
\(G_T(\tau\alpha) = U_L(T_{p}) \,(T_{p} - T_a), \quad U_L = U_t(T_p) + \frac{k_b}{L_b} + U_e\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(G_T\) | Radiation on the collector | W/m² |
| \((\tau\alpha)\) | Transmittance–absorptance product | - |
| \(N\) | Number of glass covers | - |
| \(\varepsilon_p\) | Plate emittance (selective 0.1, black paint 0.95) | - |
| \(\varepsilon_g\) | Glass emittance | - |
| \(\beta\) | Collector slope | rad |
| \(T_a\) | Ambient temperature | K |
| \(h_w\) | Wind heat transfer coefficient | W/(m²·K) |
| \(k_b\) | Back insulation conductivity | W/(m·K) |
| \(L_b\) | Back insulation thickness | m |
| \(U_e\) | Edge loss coefficient | W/(m²·K) |
| \(T_{boil}\) | Boiling point of the collector fluid at system pressure | K |
| \(T_{p,stag}\) | Stagnation plate temperature | K |
| \(U_L\) | Loss coefficient at that temperature | W/(m²·K) |
| \(U_t\) | Top loss coefficient | W/(m²·K) |
| \(S\) | Absorbed radiation | W/m² |
| \(T_{boil} - T_{p,stag}\) | Margin to boiling (negative = boils) | K |
Method and standards
No-flow energy balance with a temperature-dependent loss coefficient.
Where it is used
- Overheat protection design.
- Choosing heat transfer fluids and system pressure.
Common mistakes
- Using a constant loss coefficient measured at normal temperatures.
- Forgetting the summer worst case.
Assumptions and limits
- Steady state, clear sky, Klein's correlation range.
References
- Stagnation energy balance with Klein's top-loss equation
Questions and answers
Why does a selective absorber stagnate so hot?
Its low emittance cuts radiation loss, so the plate must get much hotter before losses balance the absorbed sunlight; 150–200 °C is common.
What happens to glycol at stagnation?
Above about 140 °C propylene glycol degrades and the fluid may boil; systems need relief valves, expansion volume or drain-back.
What do the defaults represent?
An illustrative summer case: 1,050 W/m² on a single-glazed selective collector (τα 0.80) at 35 °C ambient with a fluid boiling at 140 °C.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.