Worked example
Example: Horizontal 40 mm gap, 90 and 40 C (properties at 65 C). The inputs, in the units selected above:
| Input | Value |
|---|---|
| Hotter (lower) plate temperature | 90.000 °C |
| Colder (upper) plate temperature | 40.000 °C |
| Plate spacing | 40.000 mm |
| Tilt from horizontal (0–75°) | 0 ° |
| Air conductivity at the mean temperature | 0.029300 W/(m·K) |
| Air kinematic viscosity at the mean temperature | 1.9400e-05 m²/s |
| Air thermal diffusivity at the mean temperature | 2.7600e-05 m²/s |
Applying the formula below gives:
| Result | Value |
|---|---|
| Rayleigh number | 173,321 |
| Nusselt number | 4.5237 |
| Convection coefficient | 3.3136 W/(m²·K) |
| Convective flux across the gap | 165.68 W/m² |
Open this example in the calculator and change any input.
Formula
\(Ra = \frac{g\beta'\Delta TL^3}{\nu\alpha}, \quad \beta' = \frac{1}{T_m}\)
\(Nu = 1 + 1.44\left[1 - \frac{1708(\sin 1.8\beta)^{1.6}}{Ra\cos\beta}\right]\left[1 - \frac{1708}{Ra\cos\beta}\right]^+ + \left[\left(\frac{Ra\cos\beta}{5830}\right)^{1/3} - 1\right]^+\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(T_1\) | Hotter (lower) plate temperature | K |
| \(T_2\) | Colder (upper) plate temperature | K |
| \(L\) | Plate spacing | m |
| \(\beta\) | Tilt from horizontal (0–75°) | rad |
| \(k\) | Air conductivity at the mean temperature | W/(m·K) |
| \(\nu\) | Air kinematic viscosity at the mean temperature | m²/s |
| \(\alpha\) | Air thermal diffusivity at the mean temperature | m²/s |
| \(Ra\) | Rayleigh number | - |
| \(Nu\) | Nusselt number | - |
| \(h\) | Convection coefficient | W/(m²·K) |
| \(q\) | Convective flux across the gap | W/m² |
Method and standards
Hollands' correlation for inclined air layers heated from below.
Where it is used
- Top loss of collectors and double glazing.
- Choosing the absorber-to-cover gap.
Common mistakes
- Using properties at the wrong temperature.
- Applying it to a layer heated from above (stable, Nu = 1).
Assumptions and limits
- Air, tilt 0–75°, heated from below.
Questions and answers
Why is there an optimum plate spacing?
Too small a gap conducts heat; too large a gap allows strong convection cells. Spacings of 20–40 mm are usual.
What about vertical gaps?
The correlation stops at 75°; Designers recommend using the 75° value for vertical surfaces.
What do the defaults represent?
An illustrative case: Horizontal 40 mm gap, 90 and 40 C (properties at 65 C). Replace the inputs with your own data.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Duffie and Beckman, Solar Engineering of Thermal Processes, 4th ed. (Wiley, 2013), sec. 3.11, eq. 3.11.4 (Hollands, Unny, Raithby and Konicek, 1976) and Example 3.11.1