f-Chart Monthly Solar Fraction for Liquid, Air and Water Systems

Monthly fraction of a heating or hot-water load met by an active solar system from the f-chart X and Y groups, with storage, airflow and load exchanger corrections.

Process steam and utilitiesFood, dairy and textile

Inputs

Examples: Air system, 30 m2, 15 L/s per m2, 0.3 m3 pebbles per m2, MarchWarm-climate water heater: 4 m2, 1.2 GJ December load, 18 MJ/m2, 15 C

Accepted: 0.5 to 100,000 m²
Accepted: 5 to 100 %
Accepted: 0.1 to 30 W/(m²·K)
Accepted: 30 to 100 %
Accepted: 50 to 100 %
Accepted: 0 to 40 MJ/m²
Accepted: 28 to 31
Accepted: -43.15 to 46.85 °C
Accepted: 0.001 to 1,000,000 GJ
Accepted: 10 to 600
Accepted: 0.1 to 100
Accepted: 1 to 50
Accepted: 0.05 to 2
Accepted: 26.85 to 96.85 °C
Accepted: 0 to 36.85 °C

Results

For the year, repeat for each month and divide the sum of f·L by the sum of L.

Loss group X1.1535
Gain group Y0.34164
Corrected X1.2234
Corrected Y0.34164
Fraction of the month's load met by solar25.965%
Solar energy delivered in the month5.1929GJ

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Air system, 30 m2, 15 L/s per m2, 0.3 m3 pebbles per m2, March. The inputs, in the units selected above:

InputValue
System typeAir, space and water heating (pebble bed)
Collector area30.000 m²
Collector F_R(τα)_n50.000 %
Collector F_R U_L2.9000 W/(m²·K)
Heat exchanger and pipe factor100.00 %
Monthly average to normal (τα) ratio (one cover 0.96, two 0.94)93.000 %
Monthly average daily radiation on the collector15.800 MJ/m²
Days in the month31.000 -
Monthly average ambient temperature1.0000 °C
Monthly heating and hot-water load20.000 GJ
Storage per m² of collector, litres of water (liquid; standard 75)75.000 -
Load heat exchanger parameter (liquid space heating; standard 2)2.0000 -
Air flow per m² of collector, L/s (air; standard 10)15.000 -
Pebble bed per m² of collector, m³ (air; standard 0.25)0.30000 -
Hot water delivery temperature (water only)60.000 °C
Mains water temperature (water only)11.000 °C

Applying the formula below gives:

ResultValue
Loss group X1.1535
Gain group Y0.34164
Corrected X1.2234
Corrected Y0.34164
Fraction of the month's load met by solar25.965 %
Solar energy delivered in the month5.1929 GJ

Open this example in the calculator and change any input.

Formula

\(X = F_RU_L\frac{F'_R}{F_R}(T_{ref} - \bar T_a)\Delta t\frac{A_c}{L}, \quad Y = F_R(\tau\alpha)_n\frac{F'_R}{F_R}\frac{(\bar{\tau\alpha})}{(\tau\alpha)_n}\bar H_TN\frac{A_c}{L}, \quad T_{ref} = 100\,^\circ\text{C}\)

\(f_{liquid} = 1.029Y - 0.065X - 0.245Y^2 + 0.0018X^2 + 0.0215Y^3, \quad f_{air} = 1.040Y - 0.065X - 0.159Y^2 + 0.00187X^2 - 0.0095Y^3\)

\(\frac{X_c}{X} = \left(\frac{V_s}{75}\right)^{-0.25}, \quad \frac{Y_c}{Y} = 0.39 + 0.65e^{-0.139(UA)_h/\varepsilon_LC_{min}}, \quad \frac{X_c}{X} = \frac{11.6 + 1.18T_w + 3.86T_m - 2.32\bar T_a}{100 - \bar T_a}\)

Variables

Symbol Meaning SI unit
\(\text{system}\) System type -
\(A_c\) Collector area m²
\(F_R(\tau\alpha)_n\) Collector F_R(τα)_n -
\(F_RU_L\) Collector F_R U_L W/(m²·K)
\(F'_R/F_R\) Heat exchanger and pipe factor -
\((\bar{\tau\alpha})/(\tau\alpha)_n\) Monthly average to normal (τα) ratio (one cover 0.96, two 0.94) -
\(\bar H_T\) Monthly average daily radiation on the collector J/m²
\(N\) Days in the month -
\(\bar T_a\) Monthly average ambient temperature K
\(L\) Monthly heating and hot-water load J
\(V_s/A_c\) Storage per m² of collector, litres of water (liquid; standard 75) -
\(\varepsilon_LC_{min}/(UA)_h\) Load heat exchanger parameter (liquid space heating; standard 2) -
\(\dot V/A_c\) Air flow per m² of collector, L/s (air; standard 10) -
\(V_p/A_c\) Pebble bed per m² of collector, m³ (air; standard 0.25) -
\(T_w\) Hot water delivery temperature (water only) K
\(T_m\) Mains water temperature (water only) K
\(X\) Loss group X -
\(Y\) Gain group Y -
\(X_c\) Corrected X -
\(Y_c\) Corrected Y -
\(f\) Fraction of the month's load met by solar -
\(fL\) Solar energy delivered in the month J

Method and standards

f-chart correlations of Klein, from TRNSYS simulations.

Where it is used

  • Sizing collector area for domestic and institutional hot water.
  • Annual solar fraction for space-heating systems.

Common mistakes

  • Using daily instead of monthly totals.
  • Forgetting tank losses in the water heating load.
  • Using it for loads well above 60 °C.

Assumptions and limits

  • Standard system configurations; monthly averages; X and Y within the fitted range.

Questions and answers

What do X and Y mean?

Y compares the energy absorbed by the collectors in the month with the load; X compares the collector's reference losses (at 100 °C) with the load.

Can the f-chart be used for process heat?

Only for loads near 20 °C (space heating) or hot water up to about 60–70 °C; higher minimum temperatures need the φ̄,f-chart or simulation.

What do the defaults represent?

An illustrative case: Air system, 30 m2, 15 L/s per m2, 0.3 m3 pebbles per m2, March. Replace the inputs with your own data.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Duffie and Beckman, Solar Engineering of Thermal Processes, 4th ed. (Wiley, 2013), ch. 20, eqs. 20.2.3, 20.2.4, 20.3.1 to 20.3.3, 20.4.1 to 20.4.3 and 20.5.1 (Klein, Beckman and Duffie), Examples 20.2.1, 20.3.1 and 20.5.1

Related calculators